FW-2S Wiring Diagram
Connect wiring to the bases as shown in
the wiring diagram at right.
CAUTION:
Do not mix smoke detec-
tor types or dry contact closure de-
vices (including thermal detectors,
pull station or water flow devices) on
the same zone
.
CAUTION: Connect wiring to termi-
nals as shown. Do not loop wire un-
der terminals. Break wire run to pro-
vide supervision.
ADDITIONAL CAUTIONS:
●
Do not use looped wire under ter-
minals 2 and 5. Break wire run to
provide supervision of connec-
tions.
●
Do not attempt to disassemble
this factory-sealed smoke detec-
tor. The detector is not intended
to be opened for servicing.
Opening the detector head will
void the warranty.
●
To prevent detector contamina-
tion and subsequent warranty
cancellation, smoke detector must remain covered until installation area is clean and dust free.
●
See the FACP installation instructions for the maximum number of detectors permitted per zone and for specific wiring
terminal numbers.
●
Not suitable for installation in areas where air velocities exceed 300 ft/min.
●
Ensure the end-of-line device shown in Fig. 1 (and 1a) is compatible with the control panel.
INSTALLATION INSTRUCTIONS
FW-2S Smoke Detector
FW-2SHead
FW-2SBase
These installation instructions are for the
FW-2S FIREWOLF Smoke Detector
with internal sounder,
FW-2SHEAD
and
FW-2SBASE
.
CAUTION
Install this and all life safety devices in accordance with
applicable NFPA standards, local codes, and the authori-
ties having jurisdiction. Failure to follow these instructions
may result in failure of the detector to initiate an alarm con-
dition. Napco Security Systems, Inc. and the original
equipment manufacturer, are not responsible for detectors
that have been improperly installed, tested, or maintained.
For testing and cleaning information, refer to these instruc-
tions and/or call the NAPCO fax request line at (631) 842-
3291. Also refer to NFPA-72 Chapter 5 for Automatic Fire
Detectors for installation guidelines and Chapter 7 for test-
ing and maintenance requirements.
SPECIFICATIONS
SMOKE DETECTOR DATA
Detector Model
FW-2S
Type of Detector
Photoelectric
Working Voltage
8.5 - 14VDC
Voltage Waveform
Filtered DC 15% ripple max.
Maximum Surge Current
100µA
Average Standby Current
43.6µA @ 12VDC
Maximum Alarm Current
60mA
Compatibility Identifier
FW-2S
Sensitivity Test Feature
Built-In Test Feature
Control Panel Compatibility
See control panel installation instructions
Note:
As per UL listing requirements, open-area smoke detectors are intended for mounting on a
ceiling no less than 6 inches from a wall or mounting on a wall no less than 4 inches and no more
than 12 inches from a ceiling.
Detector Head Model
FW-2SHEAD
Detector Base Model
FW-2SBASE
© NAPCO 2010 WI1805A 04/10
The National Fire Protection Association (NFPA) states that a duct smoke detector must not be used as a substitute for
open-area smoke detectors. Duct smoke detectors are solely intended for use in the air handing equipment for such pur-
poses like dampers or shutting down the air handing units.
EOL
INITIATING
LOOP
UL LISTED
COMPATIBLE
CONTROL
PANEL
FIRST
FW-2SBASE
LAST
FW-2SBASE
5 2
5 2
Fig. 1. Two-Wire Multiple-station smoke detectors
FIREWOLF
FW-RM1
REVERSING
MODULE
REQUIRED
FOR
SOUNDER
OPERATION
(SEE
WI1809)
EOL
INITIATING
LOOP
UL LISTED
COMPATIBLE
CONTROL
PANEL
FIRST
FW-2SBASE
LAST
FW-2SBASE
5 2
5 2
Fig. 1a. Two-Wire Multiple-station smoke detectors when not using internal sounder.
(+)
(–) (+)
(–)
(+)
(–) (+)
(–)