10.2.
RH (humidity) threshold settings with LCD tool
It is possible to set the humidity threshold as follows:
The adjustable threshold corresponds to the dry contact # 1 threshold of the previous chapter. Dry
contact # 2 threshold is deduced from this threshold by adding 5% RH.
By default the threshold is set to 75% RH.
R S
4
8
5
E N O C E A N
> S E T T I
N G
E X I
T
In the main menu, select "
SETTING
" and press OK (Middle button).
The screen displays the following choices:
S T
E
P
S
T E
M P
>
H U M
V O C
R E
P
E A T
R E
T
U R N
Then select "
HUM
" and press OK (Middle button).
The screen displays the following choices:
7
7
%
< -
O K
-
>
Set the desired threshold by pressing more or less then confirm with OK (Middle button).
Select "
SAVE
" and press OK (Middle button) to save the setting
> S A V E
C A N C E L
Press OK (Middle button) and the following confirmation message is then displayed.
S A V E D