0x001B
Enum8,
reportable
Set device supported operation type, here only supports Heating Only(0x02)
ControlSequenceOfOperation
0x0029
Map16,
read-only,
reportable
Indicates the relay on/off status, here only supports bit0( Heat State)
HVAC relay state/ ThermostatRunningState
Proprietary Attributes:
Attribute
Type
Description
0x1000
ENUM8,
reportable
OLED brightness when operate the buttons:
OperateDisplayLcdBrightnesss
Value=2 : High Level
Value=0 : Low Level
Value=1 : Mid Level(default)
Manufacturer
code
0x1224
0x1001
ENUM8
reportable
ButtonVibrationLevel
Value=0 : off(default)
Value=1 : Low Level
Key beep volume & vibration level:
Value=2 : High Level
0x1224
0x1002
ENUM8
reportable
FloorSenserType
Value=5 : NTC 12K/25
Value=4 : NTC 100K/25
Value=3 : NTC 50K/25
Select external (Floor) sensor type:
Value=1 : NTC 10K/25 (Default)
Value=2 : NTC 15K/25
0x1224
0x1003
ENUM8
reportable
ControlType
Value=0 : Room sensor(Default)
Value=1 : floor sensor
Value=2 : Room+floor sensor
The referring sensor for heat control:
0x1224
0x1007
ENUM8
reportable
Value=3 : Away mode
Value=0 : OFF
Value=2 : Auto mode –schedule (default)
ModeAfterDry
The mode after Dry Mode:
Value=1 : Manual mode
0x1224
0x1008
ENUM8
reportable
Value=1 : Floor Temp
Value=0 : Room Temp (Default)
TemperatureDisplay :
0x1224
0x1009
INT8U
reportable
WindowOpenCheck
The threshold to detect open window, range is 0.3-8, unit is
0.5ºC,
0 means disabled, default is 0
0x1224
0x1006
INT8U
reportable
The duration of Dry Mode, range is 5-100, unit is min.
Default value is 5.
DryTime
0x1224
0x1005
INT8S,
reportable
The temp compensation for the external (floor) sensor, range
is -30-30, unit is 0.1°C. default value 0
FloorSenserCalibration
0x1224
0x1004
ENUM8
reportable
Value=0 : default mode
The mode after reset power of the device:
Value=1 : last status before power off (Default)
PowerUpStatus
0x1224