Matsushita Electric Works Fire & Security Technology AB
MEW00442
Rev: -
Operating Instructions EBL512, V1.44.x
98
30.4
Re-connect Loop (H8/S3)
Disconnected (disabled) loops / zone lines are indicated by LED
"Disabled" and listed in menu H4/U1.
BS4 loop require an Autronica interface board 1584 in the control
unit. DET8 "loop" require an 8 zones expansion board 1580 in the
control unit.
Action
Text in display
Comments
"Access"
According to chapter
"Access code for
maintenance", see page 95.
Scroll to menu S3.
Re-connect Loop
ACCEPT? S3
"A"
Re-connect type: 0 (0=COM, 1=BS4,
2=DET8, 3=Loop Unit) ACCEPT?
Push:
"0"=COM loop
"1"=BS4 loop
"2"=Expansion board 1580
"3"=Addr. zone interface
2226 / 2335. Push "A" to
accept.
Re-connect COM-Loop: 0, CU: 00
ACCEPT?
Re-connect BS4-Loop: 0, Board: 0,
CU: 00 ACCEPT?
Re-connect DET8-input: 0, Board: 0,
CU: 00 ACCEPT?
"A"
Depending on the
chosen type, 0, 1, 2 or
3, the following will be
shown:
Re-connect input technical no.: 000000
ACCEPT?
Write the required
numbers. Push "A" to
accept.
"A"
Re-connect type: 0 (0=COM, 1=BS4,
2=DET8, 3=Loop Unit) ACCEPT?
Continue to re-connect or
push "Return" to menu S2.
LED "Disabled" will be
turned off if there are no
other disablements in the
system.
"Return"
Re-connect Loop
ACCEPT? S3
Scroll or push "Return" to
return to menu H8. Scroll
or push "Return" to logout.