CRITICAL OPERATION CONDITIONS OF THE MOBILE AIR CLEANER UNIT W / HEPA FILTER

• 

DO NOT TOUCH 

the HEPA filter media. Damage to filter media may void the filter warranty. The screen is to protect against 

accidental contact with the filter. Never place objects on the filter. Always transport or lift the filter by its frame. 

•  Prior to powering the unit, verify that it is wired to the correct power supply. The rating plate label located on the electrical 

box cover shows the electrical data.

•  For replacement parts refer to the model number and serial number on the rating plate label located on the electrical box.

REPLACEMENT PART NUMBERS

When ordering replacement parts, please include unit model & serial number and P.O.# if available.

WARNING  – TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK OR INJURY TO 

PERSONS; ALLOW ONLY QUALIFIED TECHNICIANS TO INSTALL AND SERVICE THE 

UNIT. ALL PERSONS SHOULD OBSERVE THE FOLLOWING:

a)  Before servicing or cleaning unit, disconnect and lock-out power at the service panel to prevent electric shock or 

injury if the power is accidentally turned on. 

 

Installation work and electrical wiring must be completed by qualified persons in accordance with all applicable 

codes and standards.

•  If this unit is to be installed within close proximity to water, mark the unit in accordance with applicable codes and 

standards.

•  This unit is to be used only as intended by the manufacturer. If you have any questions regarding the use, installation 

or operation of this unit; contact the manufacturer:

  Nailor Industries of Texas, Inc.

  4714 Winfield Road, Houston, TX 77039

  Tel.: 281-590-1172

 nailor.com

Part #

Part Description

V H1-1791

Motor

V H1-0900

Blower

MAC700HEPA

24 x 24 x 6 (610 x 610 x 152) HEPA Filter

MAC700PREFILTER

24 x 16 (610 x 406) Pre-Filter

MACUVC20

UV Light

V H1-3004

UV Light Ballast

V H1-3017A

Safety Interlock Switch

V H1-2964

0 - 10 V Speed Controller

V H1-3003 A, B, C & D

Illuminated ON / OFF Switch

V H1-3016

UV-C Hour Counter

Summary of Contents for MAC-700

Page 1: ...Mobile Air Cleaner Unit w HEPA Filter Model MAC 700 Read completely and save these instructions for future reference M A N U A L M A N U A L I O M Installation Operation Maintenance ...

Page 2: ...RY TO PERSONS ALLOW ONLY QUALIFIED TECHNICIANS TO INSTALL AND SERVICE THE UNIT ALL PERSONS SHOULD OBSERVE THE FOLLOWING a Before servicing or cleaning unit disconnect and lock out power at the service panel to prevent electric shock or injury if the power is accidentally turned on Installation work and electrical wiring must be completed by qualified persons in accordance with all applicable codes...

Page 3: ...OULD OBSERVE THE FOLLOWING a Eye damage may result from directly viewing the light produced by these lamps Never look at the lamps while they are on lit or illuminated To reduce the risk of exposure to UV radiation turn off all switches and disconnect power to all UV C devices before service or take UV radiation protective measures for personnel during servicing b Before servicing or cleaning unit...

Page 4: ...system The MAC 700 is designed to pull air from all sides to increase its ability to collect biomass and dust from the floor The air will travel through a MERV 10 pre filter which captures large particles HEPA filter and UV C light before recirculating purified near sterile air up into the room The final 6 152 mm HEPA filter provides filtration that is 99 99 effective in the removal of microbial c...

Page 5: ... resistant bases and will not produce ozone SAFETY INTERLOCK SWITCH MAC 700 includes mechanical interlock switches to ensure that the UV C assembly will be de energized when the door is opened Before UV C installation make sure the interlock switch is installed and properly wired to the control box Figure 2 Safety Interlock Switch Step 1 Handle UV C fixturing wearing soft cloth gloves and safety g...

Page 6: ...ation emitted by the bulbs will degrade over the 9 000 operating hours time and will no longer provide the intended benefit however the characteristic blue glow may still be seen and generated HOUR METER AND RESET BUTTON MAC 700 is equipped with an hour meter that counts the number of hours that unit has been On The UV C lamps should be replaced when the hour meter number reaches to 9 000 After re...

Page 7: ...ag in an outdoor trash can Step 1 Open the unit door using square head door key shipped with unit Two keys shipped with unit Step 2 To remove the HEPA filter rotate all three plastic knobs counterclockwise all the way up and loose the filter clips Lift the HEPA filter out of the unit Step 3 Unpack the new filter and inspect shipping damage If damage is found do not install in unit call the manufac...

Page 8: ... right to change any information concerning product or specification without notice or obligation CONTROL BOX The MAC 700 contains a 11 x 8 279 x 203 control box that includes terminal blocks and transformer reset button and UV lights ballast Figure 6 Control Box Layout ...

Page 9: ...UV LIGHT UV LIGHT 10 NC NO COM 0 DOOR PANEL SAFETY SWITCH SPEED CONTROLLER RESET BUTTON HOUR METER 2 1 4 3 4 3 120 1 60 J BOX 8X6X4 SO CORD SIT 16 3 L1 N GND 4 3 2 1 BAS ALARM GND NEUTRAL BAS ALARM BK WH WH WH BK WH BK RD OFF ON BK YE GND YE YE TRANSFORMER 120 V 24 VAC CLASS 2 JUMPER WIRE ONLY 120 V BK BK RD YE YE LIGHT ON OFF SWITCH PRESSURE SWITCH LED SWITCH BK BN OR OR RD RD BK BN BK RD RD BK F...

Page 10: ... GN GN UV LIGHT UV LIGHT 10 2 3 0 DOOR PANEL SAFETY SWITCH SPEED CONTROLLER RESET BUTTON HOUR METER 2 1 4 3 4 3 120 1 60 SO CORD SIT 16 3 L1 N GND 4 3 2 1 WH WH BK WH BK WH RD YE BL WH BL RD BK OR YE GND YE YE TRANSFORMER 120 V 24 VAC CLASS 2 JUMPER WIRE ONLY 120 V BK RD BK RD YE BL BK RD LIGHT ON OFF SWITCH PRESSURE SWITCH LED SWITCH RD YE YE YE RD RD RD YE BK RD RD BK FRONT VIEW YE BL BK RD TOP ...

Page 11: ...th pathogens they disrupt the pathogens surface proteins rendering them inactive The technology delivers indoor air that s free of ozone and other harmful by products PRODUCT DESCRIPTION This device is an auto cleaning device handles up 2400 CFM and doesn t require maintenance with multiple mounting options STANDARD FEATURES INCLUDE Universal Voltage Input In Line ON OFF Switch Magnets for ease of...

Page 12: ...ning cycle button once 6 While cleaning is in progress press and hold the cleaning cycle button for 5 seconds 7 After LED light started flashing pressing the cleaning cycle button again will change the days between cleaning 8 The number of flashes indicates the cleaning interval in days 3 flashes 3 days 5 flashes 5 days CAUTION NEVER TOUCH BRUSHES WHILE OPERATING SHOCK MAY OCCUR TROUBLESHOOTING Th...

Page 13: ...bove steps to reassemble the motor blower assembly into the unit TROUBLE SHOOTING WARNING Disconnect the unit from the electrical power source before attempting to service the unit Unit will not run Confirm that the power cord is plugged into the building receptacle and power is present Confirm illuminated ON OFF push button is pushed in Check the speed controller and note that 1 Motor Blower is d...

Page 14: ...r o l a n d D i s t r i b u t i o n S o l u t i o n s n a i l o r c o m Calgary Canada Tel 403 279 8619 Fax 403 279 5035 Houston Texas Tel 281 590 1172 Fax 281 590 3086 Toronto Canada Tel 416 744 3300 Fax 416 744 3360 Las Vegas Nevada Tel 702 648 5400 Fax 702 638 0400 ...

Reviews: