3.3 MAIN MENU continued
Flow Configuration
The flow configuration menu provides access to modify the
application specific parameters.
IMPORTANT NOTE
All transmitters are factory configured for the intended
application. Changes to the factory configuration should
not be required. A Factory Set-Up Sheet is provided with
each transmitter and provides the details for all factory
configured parameters.
Measurement Type
Indicates whether the probes are installed in a ducted or a
fan inlet application. Ducted applications can be rectangular,
circular or flat oval. For fan inlet applications, the transmitter
can be used with single fan inlets, double fan inlets or multiple
inlet (same size) fan walls. One transmitter accepts up to 32
sensors; typically, there are two sensors per fan inlet, optional
construction uses one sensor per inlet (for fan walls).
Flow Configuration - Ducted
Select the proper duct shape (rectangular, flat oval or circular).
Enter the duct dimensions (inches or millimeters).
Area (cross-sectional duct area) is automatically calculated.
Enter the Max Flow (maximum airflow) in CFM or L/s.
Flow Configuration - Fan Inlet
Select the number of fan inlets being measured (max = 32).
Shape is automatically set to Circular.
Enter the diameter of the fan inlet(s).
Area (cross-sectional duct area) is automatically calculated.
Enter the Max Flow (maximum airflow) in CFM or L/s.
Display Configuration
This screen allows the user to set parameters on various lines
of the display.
There are four display lines on the Airflow G5.
Line 1
- Flow (typical), Velocity or Temperature
Line 2
- Velocity, Flow or None
Line 3
- Temperature, Flow or None
Line 4
- Custom ID or None. This field is settable over BACnet
or through the Service Menu. It is typically used to describe the
transmitter location in the building.
Brightness
Allows the user to set the brightness of the display in real time.
Inactivity Timeout
- The time period which holds the display in
menu mode. When the timer expires, the display is returned to
the main display screen showing the process values.
IMPORTANT NOTE
The optional true dual channel version of the Airflow G5
only displays flow.
Page 14
3/21 IOM-ELECTRA-FLO-INST
Nailor Industries Inc. reserves the right to change any information concerning product or specification without notice or obligation.
1.25
FLOW CONFIGURATION
MEAUREMENT TYPE:
SHAPE:
HEIGHT (IN.):
WIDTH (IN.):
AREA (FT
2
):
MASS FLOW (CFM):
ENT - ACCEPT ESC - LEAVE UP/DN - CHANGE
DUCTED
RECTANGULAR
6.0
30.0
2000.0
1.25
FLOW CONFIGURATION
MEAUREMENT TYPE:
FAN INLETS:
SHAPE:
DIAMETER:
AREA (FT
2
):
MASS FLOW (CFM):
ENT - ACCEPT ESC - LEAVE UP/DN - CHANGE
FAN INLET
CIRCULAR
6.0
2000.0
60 MIN.
DISPLAY CONFIGURATION
LINE 1:
LINE 1:
LINE 1:
LINE 1:
BRIGHTNESS:
INACTIVITY TIMEOUT:
ENT - ACCEPT ESC - DEL/LEAVE UP/DN - CHANGE
FLOW
TEMPERATURE
ID
100%
VELOCITY