Page 13
3/21 IOM-ELECTRA-FLO-INST
Nailor Industries Inc. reserves the right to change any information concerning product or specification without notice or obligation.
Service Menu Selection
Description
Password Configuration
Enable/disable and change password
Total System Scan
Displays sensor enabled/disabled status
Sensor Enable/Disable
Enable or disable system sensors
Sensor Data Scan
Displays individual sensor data
Sensor Alert Scan
Displays alert codes for each sensor
Custom ID
Configure ID (tag) of unit (also device name displayed in BACnet)
Restore Factory Setting
Restores display settings to original factory setup
Product Information
Displays product information (Serial number, Work Order #, etc.)
Configure Probes vs. Nodes
Configure number of probes and sensors per probe
Service Menu System 1 and System 2 (Dual Channel Version Only)
Network Configuration
Description
Network Configuration
Configure BACnet MS/TP or MODBUS RTU Network Connection
3.3 MAIN MENU
Density Compensation
- Density compensation can be
selected to be actual flow or flow corrected to standard
conditions. The default factory setting is for actual conditions.
The Airflow G5 also allows for inputting the site elevation,
which will add density compensation for average atmospheric
pressure based upon elevation above sea level.
Select System of Units
- US or SI units can be selected. US
units will display in CFM and °F. SI units will display in L/s and °C.
IMPORTANT NOTE
When changing between US and SI units, the flow
configuration information will need to be converted and
updated. This is not done by the transmitter. The user must
convert and input.
Select Units of Measure
- US and SI velocity and flow units
can be selected.
DENSITY COMPENSATION
CONDITIONS:
SITE ELEVATION:
ENT - ACCEPT ESC - DEL/LEAVE UP/DN - CHANGE
STANDARD
0
SYSTEM OF UNITS
SYSTEM:
ENT - ACCEPT ESC - DEL/LEAVE UP/DN - CHANGE
US
TEMPERATURE
VELOCITY
FLOW:
UNITS OF MEASURE
ENT - ACCEPT ESC - DEL/LEAVE UP/DN - CHANGE
DEG F
SCFM
SFPM
SCFM