Table 11 : Profibus cable type A features
Parameter
Value
Wave resistance
135 ... 165 Ohm
Capacitance per unit length
< 30 pf/m
Loop resistance
< 110 Ohm/km
Cable wire diameter
> 0.64 mm
Cable wire cross-section
> 0.34 mm²
Profibus Electrical Connection
Profibus-IN (2)
Profibus-OUT (3)
Figure 24 : Profibus connection diagram
NDRA91
P M12 connector
Profibus-Parameter
With the help of a GSD-file, a PB master creates parameters for the slave, and
has to send these data at least once to the slave before the slave can be used
for the cyclical data exchange. The slave is programmed with sufficient
tolerance for being usable only with the 7 byte standard PB parameters (also
without profile specific user parameters).