D.4.3)  Minute Adjustment of depth coverage

 

 

 

 

Adjust the minute setting to move the detection area in close to the doors. Adjust the detection area 

 

 

by sliding the minute area adjustment knob.  

 

 

 

 
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

   
 

 

Note: Do not over tighten the adjustment knob 

 

 

 

 

The direction where detection area is tilted toward the door is regarded as minus (-).  There are 9 

 

 

adjustment positions within the range between –4 to +4 degrees.  

 

 

If the mounted height is 8 ft, each adjustment position (1 degree) causes the detection area to 

 

 

move about 2 inches. 

 

 

The adjustment knob is factory set to 0 degrees. 

 

 

CAUTION: 

 

 

When detection area is tilted toward the door, the bottom edge of the header can block the  

 

 

sensor pattern if the sensor is installed too high on the header. Refer to page 7.  

 

 

Do not use the adjustment knob to widen the detection area. 

 

D.4.4)  Adjusting for Width Coverage 

 
 

 

The width coverage is achieved in seven increments as shown below. Up to six increments of 

 

 

detection width can be turned off, resulting in a reduction in coverage for the entire width. This 

 

 

may prove useful for the narrower openings on single slide or swing doors. All detection  

 

 

areas except Area 4 can be turned off (see Figure 5). Under normal conditions, all seven areas 

 

 

should be used. If any detection area zone is turned off, it will be necessary to check the  

 

 

detection area to be sure the correct ANSI Standard is achieved. 

 

 

Note: Sensed areas are not true rectangles but rectangular approximations. Pattern size will be 

 

 

affected by floor surface color and texture. 

Adjustment Knob

 

Door Side 

 

(-4°)

 

 

Out Side 

 

(+4°)

  

Figure 3 — Minute Adjustment

 

DN0187

 

Width

M

o

un

tin

g

 H

e

ig

h

t

1 2 3 4 5 6 7

Figure 4 - Front view of Coverage 
Area Zones 

DN0188

 

Summary of Contents for Gyro Tech Acuvision

Page 1: ...rating Instructions contained in this manual Failure to do so may result in property damage or bodily injury Acuvision Instruction Manual WARNING Turn OFF all power to the Automatic Door if a Safety S...

Page 2: ...on detection zone 12 D 4 3 Minute adjustment of depth coverage 13 D 4 4 Adjusting for Width Coverage 13 D 4 5 Setting Width coverage 14 D 4 6 Operation Mode Set Up D 4 6 1 Mutual Interference Preventi...

Page 3: ...ion will memorize the door swing area and door position during the first activation cycle During the door cycle the Acuvision will also scan the threshold area and store this information into its memo...

Page 4: ...x Resistance load Semiconductor Relay No Detection OPEN Detection CLOSED Power failure OPEN Mounting height Max 118 above detection area Detection area when mounted at a height of 118 118 3000mm Width...

Page 5: ...al C Appearance and Dimensions Figure 1 Appearance 8 66 220mm Mounting Pitch 7 87 200mm 1 34 34mm 3 0 76mm Sensor is interchangeable with Acusensors and Acumotion 8 pin Connector Dip Switches 1 8 Dept...

Page 6: ...hims can be used to make the necessary adjustments The unit must be mounted such that it detects the door and still provides adequate threshold protection Under normal circumstances the unit will be m...

Page 7: ...to wind or stack pressure this input signal may be required in order for the sensor to recognize when the door is in the fully closed position A mechanical or magnet ic door closed switch is necessar...

Page 8: ...Quick Disconnect connector off main microprocessor harness as shown Wire nut Acuvision harness to main harness as shown below Mount the Acuvision Sensor Note Acuvision dipswitch Settings 9 ON 10 OFF D...

Page 9: ...GREY YELLOW BLUE WHITE BLACK GREEN INPUT INPUT COM OUTPUT 2 N O OUTPUT 2 COM OUTPUT 1 COM OUTPUT 1 N O HOLE ON THE HEADER COVER ACUVISION HARNESS TERMINAL 1 TERMINAL 2 NOT USED TERMINAL 5 NOT USED NOT...

Page 10: ...NUM BOARD TERMINAL BLOCK CONNECTIONS DOOR CLOSED INPUT SEE NOTE ON PG 18 ACUVISION HARNESS 12 24 VOLTS AC DC 12 24 VOLTS AC DC NOT USED BLUE WHITE BLACK GREEN OUTPUT 2 N O OUTPUT 2 COM OUTPUT 1 COM OU...

Page 11: ...ng something new in the detection area CAUTION Confirm that the wiring is correct before turning on the power Turn power off before making adjustments to the sensor D 4 Customized Settings The followi...

Page 12: ...s in field measurements procedures and conditions from ANSI standards 4 Use of spacers for mounting Depth Adjustment Lever Position 1 Position 2 Position 3 Position 4 Position 5 Figure 2 Depth of cove...

Page 13: ...ed too high on the header Refer to page 7 Do not use the adjustment knob to widen the detection area D 4 4 Adjusting for Width Coverage The width coverage is achieved in seven increments as shown belo...

Page 14: ...light intensity reflected from the floor surface in the detection area The detection area is the reference area as determined by the Acuvision Detection sensitivities can vary depending on the color o...

Page 15: ...activates unnecessarily use the lower sensitivity When low or snow sensitivity is used care must be taken to assure that adequate sensing is maintained D 4 6 4 Standstill memory time Learn Time The Ac...

Page 16: ...es within the memorized detection area whether on the floor or above the floor will generate a signal to open the door The base memory pattern will be re learned automatically after the selected memor...

Page 17: ...correct this make adjustments using the Area Minute Adjustment Mechanism to tilt the detection area in toward the door If the amber LED is blinking when door is at full open position or while door is...

Page 18: ...ensitivity See pages 16 in this Instruction Manual D 6 5 Moving items If you have a short split curtain flowerpot or any other items that may shake in the detection area the Acuvision may falsely acti...

Page 19: ...ere rain or snow falls on it ghosting or damage to the sensor may occur In this case use Acusensor Rain Cover P N 14 10278 D 6 10 Changes in background conditions If the background condition within th...

Page 20: ...Area Conditions in Detection Ar ea altered When conditions in Detection Area change the Sensor keeps on detecting as long as the time set for Presence Detection Shorten the Presence Detection Time at...

Reviews: