GT20 Wire and Programming Manual
Rev 5-7-18
P/N C-00140
Element
Unit Type Default
Value
Description
Inverse Full & Low
OFF
OFF...ON
In the event of a power failure/error, the Door Panel is opened by spring power
from any position (unless it has been locked). The position of the motor connector
is reversed with regard to the standard drive unit.
Teach must be activated after this setting has been changed.
dAxis
Full & Low
7in
2...25IN
Distance between center line of the door hinges and the mounting surface of the
Operating Assembly. dAxis is an approximate value. Depending on the installation
situation, dAxis may have to be estimated.
Teach must be activated after this setting has been changed.
Table 11
Configurator Menu: Settings for Door Panel Functions
Element
Default
Value
Description
APuGO
OFF
OFF,
2°...10°
Triggering angle for Push&Go (angle push&go).
ASES
95°
45°...95°
Lock out angle:
X
X
Angle at which swing side door mounted sensor is ignored just before open.
X
X
If Ao is changed, ASES is auomatically set to Ao.
ASER
0°
0°...60°
Lock out angle:
Angle at which push side door mounted sensor is ignored just before closing.
inac
ve
DN 1188
closed
ASES
closed
SES
open
ASER
SER inac ve
Element
Default
Value
Description
SESClo
INACTIVE ACTIVE
Sensor mounted on Swing side of Door Panel is activated or inactivated during closing cycle.
INACTIVE
EMY-IN
CL-SPR
Configuration of the Emergency terminal (break contact) (emergency input)
CL-SPR
Spring Close (Standard Application)
STOP
Stops Door Panel Closing/Opening
OPEN
Opens Door Panel
CL-MOT
Motor Close (Inverse Application)
OExSTp
OFF
OFF
N/A
X
X
Used to set one of the activation "Values" to
“sequential” mode.
X
X
Sequential mode is used to hold the door open until a second
activation is received.
X
X
One activation opens the Door Panel and a second activation is
required to close the Door Panel.
OEI
Opening
Element Inside
OEO
Opening
Element Outside
KEY
Opening
Element NIGHT
RADIO
N/A
UNLOCK
PERMAN IMPULS
When the Door Panel is first open: Momentarily unlocks Electric Lock.
PERMAN
When the Door Panel is first open: Permanently unlocks Electric Lock.
EL-Fb
OFF
OFF
Electric Lock status feedback.
N.O.
Open if unlocked (-); Closed if locked (+)
N.C.
Open if locked (+); Closed if unlocked (-)