Select Radiator Series

Installation Guide

MYSON

Revised 6/12

Summary of Contents for 100G

Page 1: ...Select Radiator Series Installation Guide MYSON Revised 6 12 ...

Page 2: ...inal purchaser is responsible for determining the suitability of the Myson product for their installation Installation and troubleshooting should be performed by a competent technician with knowledge of hydronic heating and or basic electricity Damages occurring during shipment transit storage or handling abuse neglect accident misapplication incorrect power line voltage improper water source or c...

Page 3: ...amages injuries or unsatisfactory performance of the Myson product used Information following this symbol indicates that it is important for the correct installation or use of the product Failure to heed this information may affect the performance or useful life of the product Risk of property damage or personal injury is low Information following this symbol must be followed without exception Fai...

Page 4: ...manufacturer s warranty APPLICATION Myson radiators are only for use in recirculating closed loop hydronic heating systems These radiators are not recommended for gravity systems Myson Select Radiators are designed to work with a maximum working pressure of 78 PSI and no more then 212 degrees F water temperature DO NOT USE STEAM IN THESE RADIATORS DESIGN AND LAYOUT CONDITIONS Myson Select Radiator...

Page 5: ... wall and make the angle into the radiator 5 Select Radiator Series Rough in MYSON Nominal Height Size C 12 30 9 11 16 16 40 13 5 8 24 60 21 1 2 28 70 25 7 16 Actual LKD FF LKD TRV 2 DAV12 TRV DAV12 Model Length Valves Valves Valves Valves A B B B B 40G 15 3 4 19 3 8 19 1 8 18 3 4 19 50G 19 11 16 23 5 16 23 3 16 22 11 16 22 15 16 60G 23 5 8 27 1 4 27 1 8 26 3 8 26 7 8 70G 27 9 16 31 3 16 31 1 16 3...

Page 6: ... removed and replaced by the appropriate plug vent or valve Failure to use Myson supplied plugs may result in significant water damage Select Radiator Series Connection Arrangements MYSON Preferred methods A B C and D For alternate methods E F G and H derate the radiation by 5 P Plug V Vent S Supply R Return A B C D E F G H S V S V V S P V S R R S R P P R P R R P P S S P V P V S R V V R ...

Page 7: ...ee Radiator Range Technical Specifications for Mounting Details of Radiators Copper pipe Copper pipe Copper pipe Copper pipe Copper pipe 7 Select Radiator Series Connection Options MYSON FF LAC Valve is set full open and white knob will not turn Angle only FF WAC Valve white knob can turn to open or close the valve Angle only LKD Manual valve has chrome cap that can be removed exposing an adjustme...

Page 8: ...lo tees Scoop type is placed on the supply Venturi type on the return If heating unit is below main or more than 4 feet horizontally from the main use two monoflo tees facing each other The following drawings are general examples Consult a certified heating professional for your specific application ...

Page 9: ... Radiators use 2 brackets except the 180G which uses 3 brackets Use a level to assure bracket is plumb Step 3 To install the radiator on the brackets set the top edge of the top grill into the upper part of the bracket then gently lift and snap the bottom into the lower part of the bracket Step 4 Position radiator to line up with the supply and return pipes Many MYSON products are in excess of 70 ...

Page 10: ...ntly reduce radiator s performance Attach brackets firmly to the wall using appropriate hardware Use a level to assure bracket is plumb Step 4 Lift and seat the radiator onto the brackets Nominal Height A B C 12 11 13 16 6 1 4 6 1 4 16 15 3 4 8 3 16 6 1 4 24 23 5 8 9 12 3 8 28 27 9 16 10 15 16 12 3 8 10 MYSON Select Radiator Series Concrete Wall Installation Many MYSON Radiators are in excess of 7...

Page 11: ...pple on the valve Step 6 Thread the nipple of the valve into the radiator using a 7 16 or 12mm Allen wrench CAUTION Do not over tighten and do not use a pipe wrench on ground joint Step 7 Cut the copper pipe to a correct length NOTE The pipe must fit all the way up to the stop in the valve body approx 1 into the valve body Step 8 Place compression nut on copper pipe Step 9 Place compression ring o...

Page 12: ... homeowner without such knowledge or skill take it upon him herself to attempt the installation Myson will not be responsible for any damages injuries or unsatisfactory performance of the Myson product used NOTE MYSON products have BSP male and female threads BSP threads are a straight running thread NOT tapered like NPT Myson Radiator Valves are designed with BSP threads at radiator side and NPT ...

Page 13: ...the system to prevent corrosion 2 An occasional wiping with a damp cloth using a non abrasive detergent can protect the finish of your Myson Select Panel Radiator 3 The use of abrasive cleaners will damage the surface of your radiator and void the manufacturer s warranty ADDITIVES Treatment of the primary water is not usually required in a properly designed system Treatment may be necessary if eit...

Page 14: ...14 Select Radiator Series Notes MYSON ...

Page 15: ...Select Radiator Series Notes MYSON 15 ...

Page 16: ...YSON MYSON 1 800 698 9690 948 Hercules Drive Colchester VT 05446 Fax 802 654 7022 www MysonInc com In accordance with our policy of continual product improvement we reserve the right to amend specifications without prior notification 212033 6 12 ...