mySmart MWS6-PRM-2CH Product Manual Download Page 1

 

 

 

Ceiling Microwave presence/absence detecrto2 channel 

  

Overview 

 

The MWS6 -PRM -2CH Microwave presence detector 
provides automatic control of lighting loadswith optional 
manual control. It detectsmovement using a highly 
sensitive microwave detector. This worksby emitting low 
power microwave signalsand measuring the re ections as 
the signalsbounce o moving objects. 
The detector provides two independently controlled output 
channels that can be used for avariety of applications. 

Occupancy of two independent  lighting circuitsusing 
a single detector, e.g. for essential and non 

-essential 

supplies. 
Occupancy and lux control of one lighting circuit and 
just occupancy control of a second circuit, e.g. where 
a row of luminariesby a window islux controlled 
whilst inner rows are switched on occupancy only . 
Occupancy and lux control of alighting circuit and 
just occupancy control of aventilation circuit . 
Occupancy on both lighting circuits, with separate lux 
control on each circuit. 

All functionality isfully programmable using an IRhandset. 

MWS6 -PRM -2CH 

Ceiling Microwave presence/ 

absence detector 2 channel 

MWS6 -PRM -2CH -NC 

Ceiling Microwave presence/ 

absence detector 2 channel 
normally closed 

  

Features 

 

 

Front features 

 

Mounting Bezel 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Back features 

Retaining Spring 

 
 
 
 
 
 
 
 
 
 
 
 

Sensor Lens 

which covers... 

 

Microwave Sensor 

IRReceiver 

Light LevelSensor 

Status LEDs 

 
 
 
 
 
 
 

 

Channel 2 

Connector 

MicrowaveSensor 

Detects movement within the unit’s detection range, 
allowing load control in response to changes in occupancy. 

IRReceiver 

Receives control and programming commands from an 
IR(infrared) handset. 

LightLevelSensor 

Measures the overall light level in the detection area 

Status LEDs 

The LED   ashes 

R

ed to indicate the following: 

 

Walk Test LEDactive 

when movement is detected 

Valid setting received 

 

Channel 1 Connector 

Live input and output for Channel 1. Switch input 
connection that can be used to manually override the lights 
on or o . 

Channel 2 Connector 

Live input and output for Channel 2. Common Neutral 
connection. 

 

Channel 1 
Connector 

 
 

 

Retaining Spring 

MWS6-PRM-2CH, MWS6- 
PRM-2CH-NC

 

Product Guide

 

Summary of Contents for MWS6-PRM-2CH

Page 1: ...with separate lux control on each circuit All functionality isfully programmable using an IRhandset MWS6 PRM 2CH Ceiling Microwavepresence absence detector 2 channel MWS6 PRM 2CH NC Ceiling Microwave...

Page 2: ...r the adjustable time period has elapsed In either case sensitivity to movement of the Microwave sensor can be adjusted using the Sensitivity parameter HINT To assist in setting the Sensitivity turn o...

Page 3: ...will be switching mains voltage The unit ships with presence detection as default To change to absence detection press and release the external switch 5 times within the first minute of power up The...

Page 4: ...o read back the settings stored in a device To read back individual parameters Navigate to the parameter and press the R Read button whilst pointing at the device The handset will click when the param...

Page 5: ...minaires will always be switched on at level 9 Lux off level Switch level off 9 2 5 7 4 6 9 Lux level setting to switch the luminaires off during occupancy if the ambient light level goes above the se...

Page 6: ...whether in absence or presence mode if the lights were out because of the lux level they will be immediately turned on again for at least the Lux Time Power Up State On On or Off Select No for a 30 se...

Page 7: ...olling the channels separately This option can only be used in conjunction with a VITM4 2CH Vitesse Modular marshalling box 2 position switch together Short press on Short press off A single position...

Page 8: ...vels with Respect to HumanExposureto Radio FrequencyElectromagnetic Fields3kHz300GHz IPrating IP40 Compliance EMC 2004 108 EC LVD 2006 95 EC MWS6 PRM 2CH DBB Part numbers Partnumber Description Detect...

Reviews: