12
2. Press and hold the
button 10 seconds to start the battery test. The status display
string shows “TEST”
6.6 Recycling the Used Battery:
Warning:
Never dispose the batteries in a fire. It may explode.
Do not open or mutilate the batteries. Released electrolyte is harmful to the
skins and eyes. It may be toxic. A battery can present a risk of
electrical
shock and high short circuit current.
To recycle properly the used battery, please do not discard the UPS, battery pack and
batteries into the trash bin. Please follow your local laws and regulations; you may
contact your local recycling waste management center for further information to dispose
properly of the used UPS, battery pack, and batteries.
7. Specification
7.1 Specification
Table7. Electrical Specification
Model
1513S
2018S
3027S
Capacity
VA/Watt
1500VA/1350W
2000VA/1800W 3000VA/2700W
Input
Input voltage range
0-300VAC
Frequency range
50/60Hz ±5Hz for Normal Mode
40-80Hz for Generator Mode
Output
Voltage
220/230/240VAC
Voltage Regulation
(Batt. Mode)
±5%
Frequency
50Hz or 60Hz
Waveform
Pure sinewave
Overload rating
Line Mode
≥
110% ±10%
,
Fault after 3 Minutes.
≥
150% ±10%
,
Fault after 200ms
Battery Mode
≥
110 % ±10%
,
Fault after 30 Seconds
≥
120 % ±10 %, Fault after 100ms
Internal battery
(Standard model)
Battery Type
3*12V/9AH
4*12V/9AH
6*12V/9AH
Backup Time
(at full load)
3
′
3
′
3
′
Recharge Time
4 hours to 90%
after discharged
4 hours to 90%
after discharged
4 hours to 90%
after discharged
Interface
RS-232
Yes
USB
Yes
Dry-Contact
Optional
SNMP
Optional
EPO
Optional
Table8. Indicators and Audible alarm
Indicator
AC Mode
NORM---normal mode
Backup Mode
Show “bATT” and sounding every 4 seconds
Load/Battery Level
LCD showing