background image

OPLH-94122B page 1 of 4

OPLH / OPLHACS Series

Combination Level Indicating Gage and
Critical Level Limit Switch 

High and Low Level Limit Contacts Are
Visible and Adjustable

Designed to Start and Stop Pumps to 
Maintain Specific Levels  

Indication only Murphygage

®

instrument

Available

Latching Control Relay Versions Available

Description

The OPLHC/OPLHACS Series Level
Swichgage instruments are combination
level indicating gages with adjustable low
and high limit switches. Limit switches can
be wired directly to electric pilot circuits to
operate alarms, shutdown or start/stop
pumps to maintain predetermined levels. 

Surface mount or panel mount enclosure is
available for both model series. All models
feature a 4-1/2 in. (114 mm) dial for easy
viewing. Adjustable limit switches are
accessible from front of the Swichgage
instrument.

Specialized models are available for specific
applications involving engines or electric
motors. 

OPLHC/OPLHACS
Series Swichgage instruments

include 2-adjustable, pilot duty, pointer type
contacts. Contacts have self-cleaning motion
to enhance electrical continuity. Models are
available with a rugged bourdon-tube or 316
stainless steel bellows sensing element for
greater accuracy and sensitivity in lower
ranges. 

A “freeze-proof” sensor of 316 stainless steel
with Buna-N rolling diaphragm, is available.
The “freeze-proof” sensor (OPLHAFP)
inserts approx., 2 in. (52 mm) inside a tank.  

OPLHBP/OPLHABPS

Internal latching control relays are available

to provide ON/OFF automation for electric
motor applications.

OPLHC and OPLHACS series

are avail-

able in indication only Murphygage models
(OPLHAGS). See Page 2 to determine the
model for your application.

Applications

Saltwater Disposal Systems

Waterflood Systems 

Diesel Day Tanks

Oil Storage Tanks

Basic Operation

The OPLHC/OPLHACS series operate from
static head pressure. Pressure is transmitted
to the process connection of the Swichgage
instrument. 
From here the pressure flexes the bourdon
tube or operates the 316 stainless steel bel-
lows (depending on which model you have).
The bourdon tube/bellows oper-
ates the stainless
steel rotary
geared movement
which in turn operates
the indicating pointer on
the face of the dial. When
the pointer 

(A)

closes with the

limit contact 

(B)

, a control circuit

(C)

is completed and signals an alarm and/or

shutdown or starts/stops a pump. 

Warranty

A limited warranty on materials and workmanship
is given with this FW Murphy product. A copy of
the warranty may be viewed or printed by going to
www.fwmurphy.com/support/warranty.htm

R

Selected configurations 
are third party listed. Consult
FWMurphy for details.

OPLHFC

OPLHACS

A

Adjustment

Knob

B

C

OPLH-94122B

Revised 03-06

Catalog Section 15

4-1/2 in. (114 mm) Dial 
Level Swichgage

®

instrument

Summary of Contents for Level Swichgage Instrument OPLH

Page 1: ...316 stainless steel with Buna N rolling diaphragm is available The freeze proof sensor OPLHAFP inserts approx 2 in 52 mm inside a tank OPLHBP OPLHABPS Internal latching control relays are available to provide ON OFF automation for electric motor applications OPLHC and OPLHACS series are avail able in indication only Murphygage models OPLHAGS See Page 2 to determine the model for your application A...

Page 2: ...al DPDT 24 VAC Optional DPDT 24 VDC Optional Sensing Element Bourdon Tube Bronze Brass standard Bellows 316 Stainless Steel standard Process Connections 1 4 NPT Male 1 4 NPT Female 2 NPT Male Geared Movement 300 series stainless steel Accuracy standard calibration is for water 2 first last quarters of scale 1 middle half scale 1 3 full scale OPTIONS AVAILABLE specify when ordering Environment seal...

Page 3: ...n bourdon tube models and 1 4 NPT female on bellows models Surface NOTE Panel mount square case models do not include mounting flange and include bolt circle shown in Panel Mount Enclosure versions see below 120 120 120 5 7 16 in 138 mm 2 57 64 in 73 mm Mounting Hole 4 3 4 in 121 mm diameter Process Connection 1 4 NPT Male Panel 1 4 in 6 mm dia holes 3 places on 5 13 64 in 132 mm b c bolt circle 1...

Page 4: ...lay contacts 10 A 125 VAC OPLHC OPLHACS and OPLHAFP Series Red White Black OPLHCE OPLHFC OPLHACES and OPLHAFCS Series OPLHBP and OPLHABPS Series Specify model number NOTE No designator is required for Standard configurations Also list options in alphabetical order A to Z Place a dash between each option See example below OPLHBP 2 30 TA OPLHG OPLHGE OPLHC OPLHBP OPLHAGS OPLHACS OPLHABPS OPLHAFCS OP...