Status: Enable or disable a cooling device.
o
Start temperature (diff): Sets the temperature differential from the cooling temperature
(Temperature Curve) to activate cooling. The calculated temperature to start cooling is
adjusted according to the growth-days.
NOTE
Each cooling device operates according to its own temperature (Temperature Definition).
o
Stop temperature (diff): Sets the temperature differential from the cooling temperature
(Temperature Curve) to stop cooling device.
Stop cooling device temperature = Cooling Target ± Stop temperature
o
Enable from ventilation Level: Select the level (ventilation output) to enable cooling
operation. (Default 1).
o
Humidity Limit: Enable stopping cooling at a certain humidity level.
13.2.2
C
YCLE
C
OOLING
•
Define:
o
Growth days at which the settings change.
o
Status: Enable or disable a cooling device.
o
Start temperature (diff): Sets the temperature differential from the cooling temperature
(Temperature Curve) to activate cooling. The calculated temperature to start cooling is
adjusted according to the growth-days.
NOTE
Each cooling device operates according to its own temperature (Temperature Definition).
o
Stop temperature (diff): Sets the temperature differential from the cooling temperature
(Temperature Curve) to stop cooling device.
Stop cooling device temperature = Cooling Target ± Stop temperature
o
Enable from ventilation Level: Select the level (ventilation output) to enable cooling
operation. (Default 1).
o
ON/OFF Time: Define the amount of time the cycle is ON and OFF, respectively.
o
Humidity Limit: Enable stopping cooling at a certain humidity level.
Summary of Contents for TRIO
Page 18: ... Munters AB 2020 18 Figure 5 Relay wiring detailed view Figure 6 Relay and port numbering ...
Page 86: ... Munters AB 2020 86 ...
Page 88: ... Munters AB 2020 88 4 Verify that each channel is enabled ...
Page 170: ... Munters AB 2020 170 Click to view the bird scale data ...
Page 180: ... Munters AB 2020 180 25 3 2TRIO 20 CONTAINER SPARE PARTS ...
Page 182: ... Munters AB 2020 182 25 3 3TRIO 20 DOOR CARD SPARE PARTS ...
Page 184: ... Munters AB 2020 184 25 3 4TRIO 20 MAIN CONTAINER SPARE PARTS ...
Page 196: ... Munters AB 2020 196 Figure 36 Relay and port numbering 26 2 3POWER Figure 37 Power ports ...