DIFF: Differentiation from tunnel temperature to activate cooling. When the temperature rises this
amount above the tunnel target, cooling process begins. When temperature goes back to the
tunnel target, cooling process stops.
•
%RH: As long as the hu Band are below this level the cooling operates.
•
Cooling stops only at humidity level + band. (See figure below)
•
ON/OFF: (sec) On/Off cycle by seconds.
•
Band: The cooling table has its own ‘happy zone’ for temperature and humidity that can be set at
the system parameters under cooling section. The cooling system turns on the amount above
specified in the column ‘Diff’ and turns off when the temperature drops the amount specified in the
band.
6.6
Foggers
Foggers #01
#
From
To
Diff
%RH
On
Off
1
2
08:00
10:00
20:00
18:00
3.0
5.0
85
75
30
60
90
60
The Foggers' table provides settings for the fogger system. There are up to 5 fragments allowing precise
control over this system. Several fragments can be selected for the same day.
•
FROM: (HH:MM) Start time.
•
TO: (HH:MM) End time.
•
DIFF: Differentiation from target temperature to activate foggers. When temperature raises diff
above target, fogger's process will begin. When temperature reduces back to target, fogger's
process will stop.
•
%RH: As long as the hu Band are below this level the foggers operates.
•
Foggers stop only at humidity level + band. (See figure below)
•
ON/OFF: (sec) On/Off cycle by seconds.
6.7
Light
LIGHT
#
Day
From
To
1
2
1
5
14:0010
:00
12:00
16:00
Set the on/off times according to growth day, there are up to five programmable lines.
-
+
Band
Stop
Activate
RH%
-
+
Temp.
(Diff)
Activate
Stop
Temp
Band