74
3 G 3 J V L i s t o f P a r a m e t e r s
Chapter 9
Pa-
rame-
ter
No.
Name Description
Set-
ting
range
Unit
of set-
ting
Default
setting
Changes
during
opera-
tion
Refer-
ence
page
n62 UP/DOWN
com-
mand frequency
memory
Used to store the adjusted frequency refer-
ence with the UP/DOWN function.
0: Frequency not stored
1: Frequency stored
The frequency must be on hold for 5 s
or more.
0,
1
1 0 No 6-19
n63 Torque
com-
pensation gain
Used to set the gain of the torque com-
pensation function.
The default setting does not need any
changes in normal operation.
0.0 to
2.5
0.1 1.0 Yes
6-11
n64
Motor rated slip
Used to set the rated slip value of the mo-
tor in use.
Note
Used as the constant of the slip com-
pensation function.
0.0 to
20.0
0.1 Hz Varies
with
the ca-
pacity.
Yes 6-12
n65 Motor
no-load
current
Used to set the no-load current of the mo-
tor in use based on the rated motor current
as 100%.
Note
Used as the constant of the slip com-
pensation function.
0 to 99 1%
Varies
with
the ca-
pacity.
No 6-12
n66 Slip
compensa-
tion gain
Used to set the gain of the slip compensa-
tion function.
Note
The slip compensation function is
disabled with n66 set to 0.0.
0.0 to
2.5
0.1 0.0 Yes
6-12
n67 Slip
compensa-
tion time constant
Used for the response speed of the slip
compensation function.
Note
The default setting does not need
any changes in normal operation.
0.0 to
25.5
0.1 s
2.0
No
6-12
n68 OMRON's
control
reference use
Do not change the set value.
---
---
0
---
---
n69 OMRON's
control
reference use
Do not change the set value.
---
---
0
---
---
n70 OMRON's
control
reference use
Do not change the set value.
---
---
0
---
---
n71 OMRON's
control
reference use
Do not change the set value.
---
---
2
---
---
n72 OMRON's
control
reference use
Do not change the set value.
---
---
2
---
---
n73 OMRON's
control
reference use
Do not change the set value.
---
---
10
---
---
n74 OMRON's
control
reference use
Do not change the set value.
---
---
0
---
---
n75 Low-speed
carri-
er frequency re-
duction selection
Used to select a function to reduce the car-
rier frequency when Inverter is at low
speed.
0: Function disabled
1: Function enabled
Note
Normally set n75 to 0.
0.1
1 0 No 6-4
n76 OMRON's
control
reference use
Do not change the set value
---
---
rdy
---
---
n77 OMRON's
control
reference use
Do not change the set value
---
---
0
---
---
Summary of Contents for HCUw
Page 31: ...29 Appendix ...
Page 33: ...31 Appendix B Wiring Diagrams ...
Page 34: ......
Page 35: ......
Page 36: ......
Page 37: ......
Page 38: ......
Page 39: ......
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ......
Page 48: ......
Page 49: ......
Page 50: ......
Page 51: ......
Page 52: ......
Page 53: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 57: ......
Page 58: ......
Page 59: ......
Page 60: ......
Page 61: ......
Page 62: ......
Page 63: ......
Page 64: ......
Page 65: ......
Page 66: ......
Page 67: ......
Page 68: ......
Page 69: ......
Page 70: ......
Page 71: ......
Page 72: ......
Page 75: ...45 USER S MANUAL SYSDRIVE 3G3JVSERIES ...
Page 93: ...63 3G3JV Maintenance Operations Chapter 9 Chapter 9 List of Parameters ...
Page 114: ...84 Appendix F Gas Afterheat ...
Page 119: ...89 Figure 1 Parts Location Wiring Diagram Pictorial ...