NOTE
The table displays only those inlets mapped to a potentiometer.
4. Press the +/- key. Element calibrates the inlet or curtains.
A message appears at the end of the process.
Additional information:
•
After the potentiometer calibration finishes, Element automatically calculates the opening and
closing times and enters these numbers into the Inlet & Curtain Setup screen.
•
In the event that the potentiometers fail for any reason, Element will automatically switch to
using the time to control the opening and closing.
12.1.2
U
SING
T
IME
In the System > Installation >
, define relays as Inlet or Curtain.
1. Using a timing device measure the amount of time required to completely open and close the
curtains and vents.
2. Go to System > Levels of Ventilation > Inlet & Curtain Setup.
3. Define the following parameters:
o
Inlet 1/2: Enter the time it takes to open from 0% to 100% and to close from 100% to
0%.