10.2.3
C
ONFIGURING THE
L
EVELS OF
V
ENTILATION
This screen defines how fans operate (how long, in which mode, and which fans) at each ventilation
level.
Define up to eight fans in the
, or
screens.
1. Go to System > Levels of Ventilation > Ventilation Levels.
2. Define the following parameters:
o
Level: This displays the ventilation level. The numbers are read-only.
o
Diff: Define the temperature difference from the target temperature for that ventilation
level. Range: 0-15°C Default 0
o
On/Off: Define the fans' on and off times. Range: 0-999 seconds. Default: 0.
If a level's diff is defined as 0, ventilation will still continue to rise as the
temperature rises above the target temperature.
If a level does not have a defined diff parameter, the previous level having a
defined parameter will apply.
NOTE
If either the On or Off time is defined as 0, the fan runs in continuous mode.
o
Fan Mode: Under F-1 to F-8, define each fans mode:
: Continuous
: Cycle
●: Off
3. If required, go to System > Levels > Levels of Ventilation > Set.