5.2.3.2
Configuring the Relays
Wire the relay devices to the Element as shown in Figure 7.
CAUTION
When configuring the relays ensure that no more than 70% of the relays operate
simultaneously.
After physically wiring output devices to the Element, the corresponding relays must be defined.
Defining the relays enables the system software to control their functionality.
1.
Go to System > Installation > Relays.
2. Scroll to each relay.
3. From the drop down list, select the device wired to that relay.
o
Element automatically assigns the relay a number, according to the device type. The
number of devices supports varies according to the device type.
Heater: 6
Stir Fan:1
Curtains: 2
Timer: 5
Fan: 8
Cooling: 2
Inlet: 2
o
Same as Analog (up to 8): This function controls a device using the Element's analog
output settings. Assign the relay the number of the analog output device which will
control the relay.
When the relay switch is set to Auto, the device operates according to the
analog device settings.
When the relay switch is set to On, the device operates continually at
maximum output.
When the relay switch is set to Off, the device is shut down.
o
Same as Relay (up to 8): This function controls a device using a relay device's settings.
Assign to a relay the number of the 2nd relay that controls the relay. When a relay is
defined as "Same as Relay X", the relay copies its state when it is in Auto mode.