![Munters ComDry M160L User Manual Download Page 28](http://html.mh-extra.com/html/munters/comdry-m160l/comdry-m160l_user-manual_1856903028.webp)
9.4. Technical data
Process air
(1)
Free-blowing air 50/60 Hz (m³/h)
160
Rated airflow at 40 Pa (m³/h)
150
Max. static pressure 50/60 Hz (Pa)
225
Fan motor power (kW)
0,09
Reactivation air
(1)
Heater power (kW)
0,84
Factory set reactivation temperature (Rt) limit (°C)
130
Temperature increase across heater (°C)
100
Fan motor power (kW)
0,08
Other
Sound pressure level, free blowing process fan (dBA)
58
IEC protection class (unit)
IP33
IEC protection class (electrical panel)
IP54
Fan motor winding insulation class
Class B
Drive motor winding insulation class
Class B
Rotor type
HPS
Environmental conditions
Operating temperature (°C)
0... +30
Maximum installation altitude, above sea level (m)
2000
Transport and storage temperature (°C)
-20... +70
Total power, voltage and current
Voltage (V)
115
230
Frequency (Hz)
50/60
50/60
Total power (W)
1010
1010
Current (A)
8,8
4,4
Fuse
3 AG, 250 VAC, 10
A Slow
3 AG, 250 VAC, 6 A
Slow
(1)
The specified performance is based on 20 °C and air density of 1.2 kg/m³.
ComDry M160L Dehumidifier
28