10.3.3.15 Outdoor compressor lack phase protection(PC43)
Service manual
Check the compressor three-
phase output for obvious
open circuit
Power off,then restart the unit
2 minutes later.Is it still
displaying the error code
The unit operates
normally
Check both ends of
compressor connecting
line .Are all the connections
good?
Correct the connections
Check whether the three-
phase resistance of the
compressor is symmetrical
Replace the compressor
Yes
Yes
Yes
No
No
No
Replace the main PCB
No
Trobule is solved
Yes
10.3.3.16 Outdoor unit IR chip drive failure(PC45)
Power off,then restart the unit
2 minutes later.
Replace the inverter module
PCB.
es
Y
10.3.3.17 The cooling operation or heating operation does not operate.
Potential causes
ƽ
Faulty 4-way valve
Check of 4-way, please refer to part 4 in 10.4 Trouble Criterion Of Main Parts.
10.3.3.18
When cooling, heat exchanger of non-operating indoor unit frosts.
When heating, non-operating indoor unit get warm.
Potential causes
ƽ
Faulty EXV
ƽ
Wire and piping connected in reverse.
Check of EXV, please refer to part 5 in 10.4 Trouble Criterion Of Main Parts.
MUEX-
H11 series
64
Summary of Contents for H11 Series
Page 1: ...Service manual www mundoclima com CL21400 CL21407 MULTI INVERTER SERIE H11 R32...
Page 11: ...10 MUEX 21 H11 3 MUEX 27 H11 3 Service manual MUEX H11 series...
Page 12: ...11 MUEX 27 H11 3 Service manual MUEX H11 series...
Page 13: ...12 MUEX 36 H11 4 Service manual MUEX H11 series...
Page 14: ...13 MUEX 42 H11 5 Service manual MUEX H11 series...
Page 73: ...www mundoclima com C N POLES 249 P1 08013 BARCELONA SPAIN 34 93 446 27 80 SAT 34 93 652 53 57...