10.3.1.4 Open or short circuit of temperature sensor(IDU E4/E5/EH 60/EH 61)
Check the connections
between temperature
sensor and PCB. Are the
connections good?
Check the connections
between temperature
sensor and PCB. Are the
connections good?
Correct the connections.
Correct the connections.
No
Yes
No
eplace the sensor.
Replace the sensor.
eplace the indoor PCB
Replace the indoor PCB
Measure the resistance value
of the sensor via Appendix 1
Measure the resistance value
of the sensor via Appendix 1
Is it normal?
Is it normal?
Yes
10.3.1.5 Water-level alarm malfunction(IDU EE)
If the water-level switch
is inserted well?
If the water-level switch
is inserted well?
No
Insert the water-level switch well
Insert the water-level switch well
If the water-level switch
is broken?
If the water-level switch
is broken?
Yes
Replace the water-level switch
Replace the water-level switch
Replace the water pump, If
malfunction
is
still
not
solved
Replace the water pump, If
malfunction
is
still
not
solved
Yes
No
Yes
Replace the indoor main PCB
Replace the indoor main PCB
Power off
f
f
, then restart the unit 2 minutes
later. Is it still displaying the error code?
Power off, then restart the unit 2 minutes
later. Is it still displaying the error code?
Yes
Service manual
MUEX-
H11 series
47
Summary of Contents for H11 Series
Page 1: ...Service manual www mundoclima com CL21400 CL21407 MULTI INVERTER SERIE H11 R32...
Page 11: ...10 MUEX 21 H11 3 MUEX 27 H11 3 Service manual MUEX H11 series...
Page 12: ...11 MUEX 27 H11 3 Service manual MUEX H11 series...
Page 13: ...12 MUEX 36 H11 4 Service manual MUEX H11 series...
Page 14: ...13 MUEX 42 H11 5 Service manual MUEX H11 series...
Page 73: ...www mundoclima com C N POLES 249 P1 08013 BARCELONA SPAIN 34 93 446 27 80 SAT 34 93 652 53 57...