Service manual
DC motor voltage input and output
For split type:
NO.
Color
Signal
Voltage
1
Red
Vs/Vm
280V~380V
2
---
---
---
3
Black
GND
0V
4
White
Vcc
14-17.5V
5
Yellow
Vsp
0~5.6V
6
Blue
FG
14-17.5V
For other types:
NO.
Color
Signal
Voltage
1
Red
Vs/Vm
192V~380V
2
---
---
---
3
Black
GND
0V
4
White
Vcc
13.5-16.5V
5
Yellow
Vsp
0~6.5V
6
Blue
FG
13.5-16.5V
2. Indoor DC fan motor(control chip is inside fan motor)
Power on and when the unit is in standby, measure the voltage of pin1-pin3, pin4-pin3 in fan motor
connector. If the value of the voltage is not in the range showing in below table, the PCB must have
problems and need to be replaced.