10.3.1.2 Indoor / outdoor units communication error(E1(IDU)/ E2(ODU)/ EL 01(IDU/ODU))
Indoor / outdoor units communication error
Start: Power off , then Power on the
A/C by the Breaker. (reconnect the
power wire). Is it still displaying the
error code?
Yes
No
Replacee outdoor unit PCB assembly(include
wiring) totally
Check wiring on the outdoor and indoor
terminal follow the wiring diagram. Is all
connecting correctly?
Yes
No
Measure Vs, is it moving
alternately between positive value
and negative value? (Vs is the
voltage between S and N). Refer
PIC 1
Turn on all indoor unit by remote
controller. Is all indoor unit display
error code?
Turn off the all indoor units. Is IPM
power LED or operating LED lamp
On? Refer PIC2
Yes
A
:
Is all the wiring between
terminal and Indoor PCB
connect ok?
No
Yes
A
No
Reconnect the wiring
Is indoor units number correct? Check
on the outdoor check point . (2 for dual
zone, 3 for tri zone, 4 for qua zone,5 for
qui zone). Refer PIC 4.
Yes
No first time
Yes
Yes
Replace the Indoor PCB
Power on by remote
controller, I
Is it still
displaying the error code
after 3 minutes?
Trouble is solved
No second time
No
Yes
Reconnect the wiring
No
Replace IPM board or
the outdoor main PCB
No
Is the reactor connecting
well
˛
No
Reconnect the wiring
Replace the outdoor main PCB
Yes
No
Is main board
Ā
ā
lamp on? Refer PIC 3.
Service manual
MUEX-
H11 series
42
Summary of Contents for H11 Series
Page 1: ...Service manual www mundoclima com CL21400 CL21407 MULTI INVERTER SERIE H11 R32...
Page 11: ...10 MUEX 21 H11 3 MUEX 27 H11 3 Service manual MUEX H11 series...
Page 12: ...11 MUEX 27 H11 3 Service manual MUEX H11 series...
Page 13: ...12 MUEX 36 H11 4 Service manual MUEX H11 series...
Page 14: ...13 MUEX 42 H11 5 Service manual MUEX H11 series...
Page 73: ...www mundoclima com C N POLES 249 P1 08013 BARCELONA SPAIN 34 93 446 27 80 SAT 34 93 652 53 57...