2. Refrigerant charging
Procedure:
1). Connect the charge hose to the charging cylinder, open the 2-way valve and the 3-way valve
Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the
cylinder. Make the cylinder bottom up to ensure liquid charge.
2). Purge the air from the charge hose
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air (be
careful of the liquid refrigerant).
3) Put the charging cylinder onto the electronic scale and record the weight.
4). Open the valves (Low side) on the charge set and charge the system with liquid refrigerant
If the system cannot be charge with the specified amount of refrigerant, or can be charged with a little at a
time (approximately 150g each time) , operating the air conditioner in the cooling cycle; however, one time
is not sufficient, wait approximately 1 minute and then repeat the procedure.
5).When the electronic scale displays the proper weight, disconnect the charge hose from the 3-way valve’s
service port immediately
If the system has been charged with liquid refrigerant while operating the air conditioner, turn off the air
conditioner before disconnecting the hose.
6). Mounted the valve stem caps and the service port
Use torque wrench to tighten the service port cap to a torque of 18N.m.
Be sure to check for gas leakage
Service manual
MUEX-
H11 series
Summary of Contents for H11 Series
Page 1: ...Service manual www mundoclima com CL21400 CL21407 MULTI INVERTER SERIE H11 R32...
Page 11: ...10 MUEX 21 H11 3 MUEX 27 H11 3 Service manual MUEX H11 series...
Page 12: ...11 MUEX 27 H11 3 Service manual MUEX H11 series...
Page 13: ...12 MUEX 36 H11 4 Service manual MUEX H11 series...
Page 14: ...13 MUEX 42 H11 5 Service manual MUEX H11 series...
Page 73: ...www mundoclima com C N POLES 249 P1 08013 BARCELONA SPAIN 34 93 446 27 80 SAT 34 93 652 53 57...