17
5 - POSITIONING
Check that the floor can support the weight of the unit in
operation:
A - > 287 Kg/m
2
(200)
> 310 Kg/m
2
(200S with solar)
B - > 412 Kg/m
2
(300)
> 435 Kg/m
2
(300S with solar)
5.5 ELECTRICAL OUTLET
Configuration for electric power socket ( On/Off
switch) close to the unit
The plug must be accessible at all moment.
Install the unit in the indoor space, it is not allow to install the
unit at the rainy space
If installed in inclosed space
Barrier
The unit must be located in a space >15m³, and must have
unrestricted air flow.
Make sure there is enough Installation space.
50mm larger than the diameter of
unit
Heat pump
5.6 - CONDENSATE DRAIN
Condensate may be leaked from unit if drainage pipe is
blocked, a drainage pan is recommended as shown as
following figure.
In case of rain entering to internal components of the unit, the
component might be damaged or causing physical danger.
For optimal efficiency and serviceability, the following
clearances should be maintained: 400mm on the air inlet
side, 400mm on the air outlet side, 600mm in the back, and
600mm in the front.
The installation height of power supply should be over 1.5m, if
separate the power supply from water.