PID-2303-1C

Technical Specification

UPPER   : 4 Digit 7 seg 0.56”,White LED Display
MIDDLE : 4 Digit 7 seg 0.31”,GREEN LED Display

LOWER  : 3 Digit 7 seg 0.39”,RED LED Display

PID/ ON-OFF (selectable)

Output 

 Power Supply

  Operating
Temperature

  Relative
 Humidity

100 to 250V AC,50/60 Hz, Approx 6VA

0°C To  55°C

Up to 95% RH Non Condensing

Model

Display

Size (mm)

Panel Cutout

Input

Control Action

72 (H) X 72 (W) X 85 (D) mm

68 X 68 mm

PID-2303-1C

 J TYPE/ K TYPE, 1CT

  3Relay, 1C/O Contact,5A, 230V AC S.S.R,
  12V DC approx,30mA DC
  1Relay-For Heating PID/ON-OFF Selection//S.S.R.
  2Relay-For Blower TP/ON-OFF Selection
  3Relay- For Alarm

   Protection
      Level

   
      (As per request)

IP-65 (Front side) As per IS/IEC 60529 : 2001 

OPERATING MANUAL 

PID CONTROLLER
PID 2303-1C 

PID-2303-1C

www.multispanindia.com

Page - 2

  Temperature:J type:  0 to 400°C/ K type: 0 to 500°C 
       

       Ampere : 0.0 to 30.0 A (1 CT) 
       

 
      Range

Working

  Do  all connection according to circuit diagram. 

-Relay will be working as per following modes.

1) Control Mode PID: Relay turning ON/OFF according to heat requirement of the 
     machine.  

2) Control Mode ON/OFF: Relay turns ON (and remains ON) when PV < SV. Relay turns
     OFF when PV > SV. After this there may be overshoot depending on the thermal 
     inertia of the machine. When the PV < SV Minus HYS, Relay turns ON and heating 
     is resumed.

1) Cooling Time proportional Control action: Relay turns ON/OFF as per set Cycle time
     and difference between PV and cooling SV.
2) Cooling ON/OFF control action: Relay is initially OFF. When PV > SV, Relay turns ON 
     and when PV < SV Minus HYS relay turns OFF.   

1) Heater Break alarm: - If the current of the Heater < AMP SV (unhealthy condition)
     then Relay turns ON and Upper Display will show 

,

 

middle display will blink

hbr

     showing 

. To manually turn off Relay, press ENT key 4 sec. Display will continue 

h

     showing 

 till the fault is rectified.

hbr

2) Cold start (CS) alarm: Relay is initially OFF. When PV > Alarm SV, Relay turns ON. 
     When PV < Alarm SV MINUS HYS, Relay turns OFF.

3) High Alarm: Relay is initially OFF. When PV > Alarm SV, Relay turns ON , And remains 
    ON up to set Alarm time. Alarm is reset when temp. of PV < Alarm SV MINUS HYS. 
    This action will repeat whenever temp goes beyond Alarm SV.

4) Absolute -Low alarm: Relay is initially OFF. Now for once PV will go above SV, then 
     when PV < alarm SV, then alarm relay  turns ON and remains ON up to alarm time. 
     Alarm is reset when temp. of PV > Alarm SV+HYS. This action will repeat 
     whenever temp. goes beyond Alarm SV.

5) In band alarm:- Two Alarm SV has to be defined . Between these two values, Relay
     turns ON up to set Alarm time. Below the band & above the band relay turns OFF.

6) Absolute  outband alarm:- Two Alarm SV has to be defined. Relay is initially OFF.
     Once PV goes in between band value, after this if it goes below the band or above 
     the band, relay remains ON until alarm time.

     HYS= Hysteresis

    

R1-Heating 

R2-Cooling 

R3-Alarms 

Note:

 

1)

 

If Sensor Connection is reverse, Display will show 

 message.

SRE

 2) If Sensor is not connected, Display will show 

 message.

Open

 3) Set 2 is relative to Set 1. (e.g. Set1=100°C  and Set 2 = 15°C  then Set 2 is 
      becomes “115”)
 4) For Heater Break Indication, if any phase Heater breaks down than upper display will
     indicate 

 and middle display will show blinking

HBR

 h

  

P.V = Process value

S.V = Set value

Power On

All digit segment will be turned ON for 3 sec 

Previous or default sensor input will be displayed for 2 sec

Process Value
Set Value