MULTISPAN CC-12 Operating Manual Download Page 1

www.multispanindia.com

Page - 1

CC-12

OPERATING MANUAL 
CURRENT CONTROLLER             

CC-12

 Power Supply

  Operating
Temperature

  Relative
 Humidity

100 to 250V AC,50/60 Hz, Approx 4VA

0°C To  55°C

Up to 95% RH Non Condensing

Model

Display

Size (mm)

Panel Cutout

 
      Range

 
      Input

 
      Output

96 (H) X 96 (W) X 50 (D) mm

92 X 92 mm

5 To 1600 CT SELECTABLE AC

0 To 5Amp AC

1 Relay with 1 C/O,230V AC,5A

CC-12

Technical Specification

Connection Diagram

   Protection
      Level

IP-65 (Front side) As per IS/IEC 60529 : 2001  

Micro Controller Based, Double Display

Working

7

5

6

1

2

3

4

NO

8

9

10

I/P

0 To 5A AC

C

NC

RELAY

L

N

 AUX.  SUPPLY

100 To
250V AC

~

 

100 
250V AC

~

 

50/60 HZ
4VA

 AUX.  SUPPLY

100 To
250V AC

~

~

 

50/60 Hz
4VA

100
250V AC

!

Input  :

Range:

 

5 to 1600 CT SELE.

0 to 5 Amp AC

(2) If low alarm mode is select then starting delay time and delay time both works.   

(1) Do all connection as show in connection diagram and turn ON Instrument.   

(3) When power ON at that time relay will turn ON after completion of starting delay time.
      this delay works only one time after power ON.

(5) When Current values is less than of SET - HYS than relay will be ON.

(6) If high alarm mode is select then only delay time will works. 

(7) initially relay in OFF condition and when current value reach at that time relay will 
      turn ON after completion of delay time.

(4) When Current values reach at  SET value or above SET value at that time 
      Delay time will be start & after completion of delay time, if process value
      Greater than set value relay must be OFF.  

ENT

SET

CC 12

Ampere

Set Value

R

Relay

0 0 0

0

0 0 0

0