PAGE 38 — DCA-100SSJU — PARTS AND OPERATION MANUAL (STD) — REV. #2 (05/03/01)
240/12
0V Hard Wire Hookup
The output terminal panel, when suppling single phase 120
volts, will provide three legs available with 222.2 amps each
on three different circuits. (See Figure 23 below.) The voltage
selector switch must be set at the single phase 240/120V
position. (See figure 22 below.)
The output terminal panel, when suppling single phase 240
volts, will provide one leg only with 111.1 amps available.
(See Figure 23 below.) The voltage selector switch must be
set at the single phase 240/120V position. (See figure 22
below.)
480/240V Hard Wire Hookup
The output terminal panel, when suppling three phase 240
volts, will provide one circuit available at 241 amps with any
two wires plus the ground. (See Figure 25 below.) The voltage
selector switch must be set at the three phase 480/277V
position. (See figure 24 below.)
The output terminal panel, when suppling 3 phase 480 volts,
will provide one circuit available at 120 amps available with
all three wires plus ground. (See Figure 25 below.) The
voltage selector switch must be set at the three phase 480/
277V position. (See figure 24 below.)
FIGURE 22. Voltage Selector Switch 240/120V Single Phase
Position
FIGURE 24. Voltage Selector Switch 480/277V Three Phase
Position
FIGURE 23. Hard Wire Hookup at 240/120V Position
FIGURE 25. Hard Wire Hookup at 480/240V Position
DCA-100SSJU — OUTPUT TERMINAL PANEL OVERVIEW
Summary of Contents for Power WHISPERWATT DCA-100SSJU
Page 2: ...PAGE 2 DCA 100SSJU PARTS AND OPERATION MANUAL STD REV 2 05 03 01...
Page 22: ...PAGE 22 DCA 100SSJU PARTS AND OPERATION MANUAL STD REV 2 05 03 01 DCA 100SSJU GENERATOR DECALS...
Page 27: ...DCA 100SSJU PARTS AND OPERATION MANUAL STD REV 2 05 03 01 PAGE 27 NOTE PAGE...
Page 91: ...DCA 100SSJU PARTS AND OPERATION MANUAL STD REV 2 05 03 01 PAGE 91 NOTE PAGE...