PAGE 30 — DCA-125SSJU SERIES (STANDARD) — PARTS AND OPERATION MANUAL — REV. #4 (06/03/03)
Figure 13. Connecting Loads
Connecting Loads
Loads can be connected to the generator by the
UVWO
terminal
lugs or the convienience receptacles. (See Figure 13). Make
sure to read the operation manual before attempting to connect
a load to the generator.
To protect the UVWO output terminals from overload, a 3-
pole, 300 amp,
main
circuit breaker is provided. Make sure
to switch
ALL
circuit breakers to the "
OFF
" position prior to
starting the engine.
DCA-125SSJU SERIES — OUTPUT TERMINAL PANEL FAMILIARIZATION
Over Current Relay
An
over current relay
(Figure 14) is connected to the main
circuit breaker. In the event of an overload, both the circuit
breaker and the over current relay may trip. If the circuit
breaker can not be reset, the
reset button
on the over cur-
rent relay must be pressed. The over current relay is lo-
cated in the control box.
Figure 14. Over Current Relay
Maximum Output
The entire load connected to the UVWO terminal lugs, duplex
and auxiliary receptacles must not exceed 110 kw in standby or
100 kw in prime output.