Inputs
The following input functions show the factory defaults with all inputs and outputs being configurable. Refer to
document number P0021 for advanced programming information. Contact your local RCT branch or distributor
for a copy of the document or for more information.
Function 1
This input is configured to have a five-second delay prior to pulsing the alert indicator and activating the alarm.
After a further 10 seconds, the alert indicator will come on solid, the alarm will remain on and activate the idle
and ETR control circuits. This circuit activates when the circuit changes state and becomes open. This input
is specifically designed for coolant level detection.
If this function is not required, pin 7 must be connected to
ground.
Note:
This function uses an AC (alternating current) circuit. This reduces electrolysis and corrosion of the
coolant level sensor. This will help to keep the probe in good working order.
Function 2
This input is configured to have a one-second delay prior to activating the corresponding alert indicator,
external audible alarm, idle and ETR control circuits. This circuit activates when the circuit changes state and
becomes open.
If this function is not required, pin 8 must be connected to ground.
Typical use: Low engine oil pressure
Function 3
This input is configured to have a one-second delay prior to activating the corresponding alert indicator,
external audible alarm, idle and ETR control circuits. This circuit activates when the circuit changes state and
becomes open.
If this function is not required, pin 9 must be connected to ground.
Typical use: High engine temperature
Function 4
This input is configured to have a one-second delay prior to activating the corresponding alert indicator,
external audible alarm, idle and ETR control circuits. This circuit activates when the circuit changes state and
becomes open.
If this function is not required, pin 10 must be connected to ground.
Typical use: Low engine oil level
Function 5
This input is configured to have a one-second delay prior to activating its corresponding alert indicator, external
audible alarm, idle and ETR control circuits. This circuit activates when the circuit changes state and becomes
open.
If this function is not required, pin 11 must be connected to ground.
Typical use: Coolant flow
Function 6
This input is configured to have a one-second delay prior to activating its corresponding alert indicator, external
audible alarm, idle and ETR control circuits. This circuit activates when the circuit changes state and becomes
open.
If this function is not required, pin 12 must be connected to ground.
Typical use: Convertor oil temperature