Quick Start Guide

QSG 900LR

WIO-900LR
wireless I/O receiver unit

Summary of Contents for WIO-900LR

Page 1: ...Quick Start Guide QSG 900LR WIO 900LR wireless I O receiver unit ...

Page 2: ...he basic steps for using your unit are 1 Connect the antenna power supply and transducer signals using the instructions in this document Power supply and transducer connection is described in the section Unit components and connections Antenna connection is described in the section Antenna installation For more information see the WIO 900L Installation Manual 2 Resetthetransmitterandreceiverunitst...

Page 3: ...egulations this module must be installed in an Electrical AND Fire enclosure This enclosure may be a single or multiple enclosures Access to the module is to be made by a Service Person only In order to comply with Electrical Safety Standards when connecting SELV AND voltages which are greater than SELV 30VAC or 60VDC together then Relay Output 2 must NOT be used in order to provide sufficient iso...

Page 4: ...ssed When you press the RSSI push button the unit shows the signal strength by lighting the LEDs from the bottom to the top Signal strength is the strength of the last message received that was addressed to this station LED Signal Strength LED Signal Strength D1 Better than 85 dBm RX Better than 100 dBm D2 Better than 90 dBm CF Better than 105 dBm D3 Better than 95 dBm PG Always on during RSSI tes...

Page 5: ...0LR receiver flashes all LEDs at medium flash i e 1 6 Hz NOTE If the LEDs do not flash you must repeat steps 1 and 2 until the LEDs flash before continuing 4 Release the RSSI push button within 5 seconds 5 Within a further 60 seconds press and hold the RSSI push button for 5 seconds until the LEDs stop flashing and then release 6 The WIO 900LR receiver lights all LEDs for 2 seconds before returnin...

Page 6: ...nds you must restart the linking process from step 1 You can now bench test your configuration before deploying 7 Safety information Thank you for selecting the WIO 900LR receiver for your telemetry needs We trust it will give you many years of valuable service To ensure your WIO 900LR receiver enjoys a long life double check ALL your connections with the user s manual before powering on the unit ...

Page 7: ...t cause harmful interference and This device must accept any interference received including interference that may cause undesired operation NOTE This equipment is suitable for use in Class 1 Division 2 groups A B C and D or non hazardous locations only 8 Unit specifications Input output Number Additional information Digital outputs 3 Voltage free contacts rated at 250 VAC 1A 30VDC 1A 2 for digita...

Page 8: ...ello Balsamo MI Italy Tel 39 0 2 61802011 Fax 39 0 2 61294560 E mail info mtl inst it Cooper Crouse Hinds Japan KK MT Building 3F 2 7 5 Shiba Daimon Minato ku Tokyo Japan 105 0012 Tel 81 0 3 6430 3128 Fax 81 0 3 6430 3129 E mail sales mtlkk co jp Cooper Crouse Hinds Korea 12F Vision Tower 707 2 Yeoksam dong Gangnam gu Seoul 135 080 South Korea Tel 82 2 3484 6795 Fax 82 2 3484 6778 MTL Instruments ...