7 Troubleshooting
7.1
Indicators at the SC2
The SC2 has got no diagnostic indications; they are only available on the basic sensor boards of SB, MSC,
MSB or MGC.
7.2
Indicators at the MC2
The 4 - 20 mA output of the MC2 can be used as diagnostic indicators.
Output current
Restart:
1 mA
Device error:
2 mA
Tolerable negative sensor drift:
3 - 4 mA
Normal measurement mode:
4 - 20 mA
Tolerable overrange:
20 - 21 mA
Overrange error:
> 21 mA
Maintenance message:
19 mA
7.3
Basic Sensor Board
Trouble
Cause
Solution
Green LED isn’t on.
Power voltage not applied.
Measure tension at X4:
(16-28 V DC) Pin 1 (+) and 2 (-)
Polarity not correct at X4.
Connect correctly.
Connector X4 not plugged in.
Check the plug.
Wire breakage
Check the wiring.
Green LED doesn’t flash.
BSB: no address
Check BSB address, address
correctly.
BSB: no field bus communication
Check field bus wiring, topology
and termination.
No measured value at the Tool or
Controller
SC not or wrongly plugged in.
Check SC plug.
SC not registered.
Register SC.
SC gas type/measuring range doesn’t
match with registered ones.
Check SC data<> registration
data for conformity.
Message at the Tool / Controller:
- 24 V DC voltage <range>
- 5 V DC voltage <range>
- Temp. <range>
- WatchDog triggered
Internal error
Replace BSB.
7.4
Sensor Cartridge (Messages at the Tool / Controller)
Measuring signal <range>
Internal error
Replace SC.
5 V DC voltage < range >
Temp. < range >
WatchDog triggered
SC Input 1
stored type
Wrong SC type at input 1
Check SC at input 1, replace it.
SC Input 2
stored type
Wrong SC type at input 2
Check SC at input 2, replace it.
SC Input 3
stored type
Wrong SC type at input 3
Check SC at input 3, replace it.