86
Calibration
GB
SUPREMATouch
7
Calibration
Sensitivity and zero point of the connected sensors must be adjusted as necessary in accordance
with the operating instructions for the types of sensors connected to the system.
Sensors which are no longer able to generate the minimum signals must be replaced.
Two calibration modes are available:
• In one mode two persons are required to perform calibrations. Person 1 operating the
SUPREMATouch and Person 2 supplying the sensors with gas. It is necessary for them to
communicate during the calibration.
• In the other mode only one person is required. This person starts the calibration, goes to the
sensors to apply gas and finally finishing the calibration back at the SUPREMATouch.
NOTICE
Observe and follow all regulations and rules regarding use of communication devices in the area
where the SUPREMATouch is installed.
7.1
Calibration Submenu
Calibration parameters for the individual inputs can be set in the calibration menu. From that point
on the calibration is controlled by the SUPREMATouch.
The window is divided into two subwindows:
•
Start calibration
•
End calibration
If an input is selected that is not already in calibration mode, the
Start calibration
window appears.
If an input is selected that is already in calibration mode, the
End calibration
window appears.
The fields
Measuring Point
and
Tag
fields are available in both windows.
Fig. 55 Start calibration
The preadjustment is applied immediately and cannot be cancelled or discarded.
Summary of Contents for SUPREMATouch MCP 20
Page 1: ...MSAsafety com Operating Manual SUPREMATouch Fire and Gas Warning Unit Order No 10121863 05...
Page 8: ...MSAsafety com User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Page 72: ...MSAsafety com Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Page 232: ...232 Dimensions GB SUPREMATouch 18 Dimensions 18 1 Rack...
Page 233: ...233 Dimensions GB SUPREMATouch 18 2 Rail mounted Modules MRO8 TS Module MRO16 TS Module...
Page 235: ...235 Dimensions GB SUPREMATouch MRO20 8 TS Module 1 3 2 69 90...
Page 236: ...236 Dimensions GB SUPREMATouch MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Page 237: ...237 Dimensions GB SUPREMATouch MRC TS Module MGT40 TS Module...
Page 238: ...238 Dimensions GB SUPREMATouch MHD TS Module MAT TS Module...
Page 241: ...For local MSA contacts please visit us at MSAsafety com Because every life has a purpose...