139
Installation
GB
SUPREMATouch
WARNING!
The normal function of the module is deactivated in the boot loader mode. This mode should
therefore only be used by the MSA service personnel!
Fig. 77 Configuration of the MBC20 Module
Configuration MBT20 Module
No configuration
Configuration in the SUPREMATouch menu
Settings/Measuring points/Sensor data
MRD Dummy Relay
Module application/function
Up to 5 relay modules can be connected (MRO8/MRO16) to the MRC module. If not all 5 relay
modules are connected, an MRD module must be plugged into each of the unused relay module
connectors. The unused relays are simulated by this module.
With an MRD module connected the driver outputs of the MGO module are provided with a fixed
load. Monitoring the driver outputs therefore allows a failure state to be recognized.
All 40 outputs of the MGO modules are monitored. Output failures (open/short circuit) are identi-
fied and are reported as a system fail.
Sensor
MFI
Measuring range
0–100 %
Units
any
Summary of Contents for SUPREMATouch MCP 20
Page 1: ...MSAsafety com Operating Manual SUPREMATouch Fire and Gas Warning Unit Order No 10121863 05...
Page 8: ...MSAsafety com User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Page 72: ...MSAsafety com Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Page 232: ...232 Dimensions GB SUPREMATouch 18 Dimensions 18 1 Rack...
Page 233: ...233 Dimensions GB SUPREMATouch 18 2 Rail mounted Modules MRO8 TS Module MRO16 TS Module...
Page 235: ...235 Dimensions GB SUPREMATouch MRO20 8 TS Module 1 3 2 69 90...
Page 236: ...236 Dimensions GB SUPREMATouch MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Page 237: ...237 Dimensions GB SUPREMATouch MRC TS Module MGT40 TS Module...
Page 238: ...238 Dimensions GB SUPREMATouch MHD TS Module MAT TS Module...
Page 241: ...For local MSA contacts please visit us at MSAsafety com Because every life has a purpose...