15.13 SUPREMA Sensor Data Sheet Series 47K-HT (3-wire)
Order No.: according to order sheet
Fig. 192
The cable screen is only connected to the SUPREMA.
Alternatively, the bridges -X1/1 -X1/2 and -X1/4 -X1/5 can be set as solder bridges on the MAT-
10-TS module.
Connection module:
MPI-WT 100/passive/3-wire/Constant current/Presetting required
Sensor
simulation module:
WT (= catalytic combustion) (Order No.: 10030263)
Attention!
Before connecting measuring head, reduce sensor current to
minimum
Connection
data:
Bridge current
280 mA
Maximum nominal current
350 mA
Power consumption
1.0 W typical (without cable length)
Cable type
3-core, 80 % screened
Maximum loop resistance
36 ohms (3.4 ohms for ATEX applications)
Maximum cable length
1000 m (at 1.5 mm
2
cross section per wire
Cable diameter
6 ... 12 mm
Cross section per wire al-
lowed
1.0 ... 2.5 mm
2
Connection box II 2 G EEx e
II/PTB 00 ATEX 1063
Order No.: 10062674
Wall angle bracket with con-
nection of potential equaliza-
tion
Order No.: 10048829
Summary of Contents for SUPREMA Touch
Page 2: ...Manual SUPREMATouch Fire and Gas Warning Unit Order No 10126972 00...
Page 7: ...SUPREMATouch 6 Contents MSA US...
Page 8: ...User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Page 104: ...Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Page 112: ...Installation and Start Up Manual SUPREMATouch Fire and Gas Warning Unit...
Page 151: ...SUPREMATouch 150 Installation MSA US Fig 79 MCP Module standard configuration...
Page 303: ...SUPREMA 302 Dimensions MSA GB 16 Dimensions 16 1 Rack...
Page 306: ...MSA AUER MSA Dimensions SUPREMA 305 GB MRO20 8 TS Module 1 3 2 69 90...
Page 307: ...SUPREMA 306 Dimensions MSA GB MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Page 308: ...MSA AUER MSA Dimensions SUPREMA 307 GB MRC TS Module MGT 40 TS Module...
Page 309: ...SUPREMA 308 Dimensions MSA GB MHD TS Module MAT TS Module...