SUPREMA Sensor Data Sheets
MSA
US
15.12 SUPREMA Sensor Data Sheet Contact
Fig. 191
The cable screen is only connected to the SUPREMA.
Connection
data:
Maximum nominal current
8 mA
Maximum nominal voltage
15 V
Power consumption
≤
1.0 W (including cable length)
Cable type
2-core, 80 % screened
Maximum loop resistance
50 ohms
Maximum cable length
2000 m (at 1.5 mm
2
cross section per wire
Cross section per wire al-
lowed
0.5 ... 2.5 mm
2
Conditions
for use:
Mounting
depending on the switch type
Ingress protection
-
Explosion protection
no
Certificate
depending on the switch type
Temperature
depending on the switch type
Humidity
depending on the switch type
Pressure
depending on the switch type
Weight
depending on the switch type
Dimensions W x D x H
depending on the switch type
Housing material
depending on the switch type
Summary of Contents for SUPREMA Touch
Page 2: ...Manual SUPREMATouch Fire and Gas Warning Unit Order No 10126972 00...
Page 7: ...SUPREMATouch 6 Contents MSA US...
Page 8: ...User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Page 104: ...Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Page 112: ...Installation and Start Up Manual SUPREMATouch Fire and Gas Warning Unit...
Page 151: ...SUPREMATouch 150 Installation MSA US Fig 79 MCP Module standard configuration...
Page 303: ...SUPREMA 302 Dimensions MSA GB 16 Dimensions 16 1 Rack...
Page 306: ...MSA AUER MSA Dimensions SUPREMA 305 GB MRO20 8 TS Module 1 3 2 69 90...
Page 307: ...SUPREMA 306 Dimensions MSA GB MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Page 308: ...MSA AUER MSA Dimensions SUPREMA 307 GB MRC TS Module MGT 40 TS Module...
Page 309: ...SUPREMA 308 Dimensions MSA GB MHD TS Module MAT TS Module...