13.1 Application/Function Safety
For the safety functions of gas warning measuring instruments, the European standards
EN 60 079-29-1, EN 50 104, EN 50 271 , and EN 50 402 have been prepared for the monitoring
of explosive gas and vapours as well as oxygen.
Additionally, if systems are operated together with microcomputers, the standard EN 61 508 must
be considered with regard to functional safety in a measuring and control application.
This standard divides the application types into Safety Integrity Levels SIL 1–4. The system must
be designed to meet the safety level required.
For operation according to SIL 4, additional conditions must be met which are not planned for the
SUPREMA for the time being.
By retrofitting modules, a non-redundant rack system can be converted to a redundant system.
There are sufficient spare slots in the rack for the additional MGO modules but not for additional
relay modules, (MTO, MRC).
The following module types are needed for retrofitting:
By adding the MCP module, operation of a second CAN bus for data acquisition and alarming as
well as the necessary double modules for data acquisition and alarming, the non-redundant sys-
tem can be converted to a redundant system.
For the EN 61 508 SIL 3 Safety Level, the SUPREMA must be operated with redundancy.
Moreover, the system as well as the MRC TS module must not be operated with a redun-
dancy whose failure rate is more than 6.73 * 10-6 1/h.
MCP Module
Central Processing
MDA Module
Data Acquisition
MAR Module
Analog Redundant
MGO Module
General Output
MRO 8 Module
Relay Output (8 Relay)
MRO 16 Module
Relay Output (2 x 8 Relay, redundant)
Summary of Contents for SUPREMA Touch
Page 2: ...Manual SUPREMATouch Fire and Gas Warning Unit Order No 10126972 00...
Page 7: ...SUPREMATouch 6 Contents MSA US...
Page 8: ...User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Page 104: ...Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Page 112: ...Installation and Start Up Manual SUPREMATouch Fire and Gas Warning Unit...
Page 151: ...SUPREMATouch 150 Installation MSA US Fig 79 MCP Module standard configuration...
Page 303: ...SUPREMA 302 Dimensions MSA GB 16 Dimensions 16 1 Rack...
Page 306: ...MSA AUER MSA Dimensions SUPREMA 305 GB MRO20 8 TS Module 1 3 2 69 90...
Page 307: ...SUPREMA 306 Dimensions MSA GB MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Page 308: ...MSA AUER MSA Dimensions SUPREMA 307 GB MRC TS Module MGT 40 TS Module...
Page 309: ...SUPREMA 308 Dimensions MSA GB MHD TS Module MAT TS Module...