7.5
Mapping BACnet Output with Device EZ Profiles
•
Open the DeviceProxy™ page.
•
Choose the Device Profile to load from the drop down menu.
NOTE: If required, click the Advanced Settings button (eye icon) to enter the Device Description and Device
Location.
•
Choose the appropriate connection and Node ID/BACnet Device Instance for both the incoming Modbus device and the
mapped BACnet output.
•
Click Add to include additional device profiles in the Configuration.
•
Repeat for all Modbus devices intended to connect to the EZ Gateway.
•
Click the Save button on the right side of the screen once all device EZ Profiles are added and then click the Restart
button to reset the system.
EZ Gateway Modbus to BACnet Start-up Guide
27