7.3.1 Using the Device Web Interface to Map BACnet Objects
NOTE: The Add button creates another blank profile that must be mapped using the Web Interface.
•
Click on the Edit button (pencil icon) next to the name of the profile to map.
•
Enter the Modbus and BACnet parameters.
NOTE: See Section
11.5 Address Types and Data Types
for additional information on Address Type.
•
Click on the Data Map tab and add the first Modbus address range.
NOTE: Check the Signed Value checkbox (right of the data map entry) if signed values are needed.
EZ Gateway Modbus to BACnet Start-up Guide
21