5 Assembly: Standard design
Maschinenfabrik Reinhausen GmbH 2015
54
4349315/00 EN
VACUTAP® VR®
Tap selector connection contacts for multiple coarse change-
over selector VRC
In the case of multiple coarse change-over selectors, special attention must
be paid when routing the cables for connecting the tap selector connection
contacts and the multiple coarse change-over selector connection contacts.
These cables should be as far away as possible from neighboring connec-
tion contacts.
► Tap selector connection contacts that face both multiple course tap se-
lector columns must have at least 3 mm of paper insulation to ensure di-
electric strength.
In this regard, please also pay attention to the dimensional drawing on which
the order is based.
Figure 38: Paper insulation
has 3 mm of paper insulation
p Connections to be insulated
Change-over selector connection contacts for reversing change-
over selector connection VRC/VRE
The (+) and (-) change-over selector connection contacts are designed as
connecting lugs with through-holes for M10 screws for reversing change-
over selector connection.
5.3.2
5.3.3
Summary of Contents for VACUTAP VR
Page 1: ...On Load Tap Changer VACUTAP VR Installation and Commissioning Instructions 4349315 00 EN ...
Page 246: ...14 Appendix Maschinenfabrik Reinhausen GmbH 2015 246 4349315 00 EN VACUTAP VR ...
Page 248: ...14 Appendix Maschinenfabrik Reinhausen GmbH 2015 248 4349315 00 EN VACUTAP VR ...
Page 266: ......
Page 267: ......