5 Assembly: Standard design
Maschinenfabrik Reinhausen GmbH 2015
52
4349315/00 EN
VACUTAP® VR®
Connecting tap selector take-off leads
Proceed as follows to connect the tap selector take-off leads:
1.
NOTICE!
Screw tap selector take-off lead to connecting piece with care.
Comply with specified tightening torque and secure screw connection.
Failure to do so may result in damage to the on-load tap-changer and
transformer.
2.
Attach screening caps to screw connection.
Figure 35: Tap selector take-off lead
Connecting tap winding and on-load tap-changer take-off
lead
NOTICE
Damage to the on-load tap-changer!
Connecting leads which place mechanical strain on the on-load tap-changer
will damage the on-load tap-changer!
► Produce connections with care.
► Do not twist connection contacts.
► Connect connecting leads without warping or deforming.
► If necessary use an expansion loop for connecting leads.
► Fit screening caps provided to screw connections.
The tap winding and on-load tap-changer take-off lead must be connected in
accordance with the connection diagram included with the delivery.
Tap selector connection contacts VRC/VRE
The selector connection contacts are indicated on the selector bars, have
crimped ends and a through-hole for M10 screws to allow the selector take-
off leads to be connected by means of cable shoes.
5.2.5
5.3
5.3.1
Summary of Contents for VACUTAP VR
Page 1: ...On Load Tap Changer VACUTAP VR Installation and Commissioning Instructions 4349315 00 EN ...
Page 246: ...14 Appendix Maschinenfabrik Reinhausen GmbH 2015 246 4349315 00 EN VACUTAP VR ...
Page 248: ...14 Appendix Maschinenfabrik Reinhausen GmbH 2015 248 4349315 00 EN VACUTAP VR ...
Page 266: ......
Page 267: ......