9 Commissioning of on-load tap-changer by transformer manufacturer
Maschinenfabrik Reinhausen GmbH 2015
212
4349315/00 EN
VACUTAP® VR®
NOTICE
Damage to the on-load tap-changer!
Damage to the on-load tap-changer by actuating the on-load tap-changer
without oil!
► Before actuating the on-load tap-changer for the first time, the tap se-
lector must be completely immersed in transformer oil and the oil com-
partment completely filled with oil.
► The on-load tap-changer can be operated in the temperature range of
the surrounding transformer oil of between -25 ° and +105 °C and with
overload up to +115 °C in accordance with IEC 60214-1.
1.
Undertake tap change operation tests across entire range of settings.
2.
NOTICE!
Make sure that in each operating position the tap position in-
dicators of motor-drive unit and on-load tap-changer (inspection window
in the on-load tap-changer head) read the same position. An incorrectly
coupled motor-drive unit will damage the on-load tap-changer.
High-voltage tests on the transformer
WARNING
Danger of death or severe injury!
Danger of death or severe injury from explosive gases under the on-load
tap-changer head cover, in the pipework system, in the oil conservator, at
the dehydrating breather opening, and from flying parts and hot oil splash-
ing!
► Ensure that there are no naked flames, hot surfaces or sparks (for ex-
ample caused by static charging) in the immediate surroundings and
that none occur.
► Ensure that the oil compartment of the on-load tap-changer is com-
pletely filled with oil.
► Only use conductive and grounded hoses, pipes, and pump equipment
that are approved for flammable liquids.
► Ensure that all the on-load tap-changer's safety equipment is ready for
use.
► Use suitable personal protective equipment/clothing.
► Keep away from the danger area during the transformer test.
► Observe applicable fire protection regulations.
► Make sure that only trained technicians perform work on the transform-
er.
It is essential that you ensure only trained, instructed expert personnel who
are familiar with and comply with the pertinent safety and technical regula-
tions, who are aware of the potential risks, and who consistently use the oc-
cupational safety equipment provided to prevent injury and property damage
are assigned to perform such a transformer test.
9.5
Summary of Contents for VACUTAP VR
Page 1: ...On Load Tap Changer VACUTAP VR Installation and Commissioning Instructions 4349315 00 EN ...
Page 246: ...14 Appendix Maschinenfabrik Reinhausen GmbH 2015 246 4349315 00 EN VACUTAP VR ...
Page 248: ...14 Appendix Maschinenfabrik Reinhausen GmbH 2015 248 4349315 00 EN VACUTAP VR ...
Page 266: ......
Page 267: ......