5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
78
5293079/01 EN
VACUTAP
®
VM-Ex
5.3.7.2.3.4 Securing on-load tap-changer head cover
1.
NOTICE!
Place on-load tap-changer head cover on on-load tap-changer
head and take care not to damage the o-ring inserted in the on-load tap-
changer head cover. A damaged o-ring leads to oil escaping and there-
fore to damage of the on-load tap-changer. Also ensure that the red trian-
gular marks on the on-load tap-changer head and the on-load tap-changer
head cover match up.
Figure 69: On-load tap-changer head cover with o-ring
2. Screw on-load tap-changer head cover using screws and washers.
Figure 70: On-load tap-changer head cover
5.3.7.2.4 Drying the on-load tap-changer
1. Connect pipe connections R and Q of on-load tap-changer head to the
kerosene vapor lead using one shared lead.