6 Functions and settings
Maschinenfabrik Reinhausen GmbH 2016
112
5163667/00 EN
TRAFOGUARD® ISM®
To configure the tap synchronization parallel operation method, you also
have to set the following parameters:
▪
Master/follower current blocking
▪
Maximum tap difference
Master/follower current blocking
You can use this parameter to activate the circulating reactive current block-
ing limit for the tap synchronization parallel operation method. The device
thereby calculates and monitors the circulating reactive current in the same
manner as for the circulating reactive current minimization parallel operation
method. The Circulating reactive current blocking [
110] parameter is used
to set the limit value.
To activate circulating reactive current blocking for the tap synchronization
parallel operation method, proceed as follows:
1.
Go to
Settings > Parameters >
Parallel operation > Master/follower
current blocking
.
2.
Select the option you want.
3.
Press the
Accept
button to save the modified parameter.
Maximum tap difference
You can use this parameter to set the maximum permissible tap difference
between followers and master on the follower.
If the tap difference is greater than the set maximum tap difference to the
master, the follower immediately blocks. The follower therefore no longer at-
tempts to reach the master's tap position. After the set delay time for parallel
operation error messages has elapsed, the follower issues the
Permitted tap
difference to master exceeded
message.
To set the maximum permissible tap difference, proceed as follows:
1.
Go to
Settings > Parameters >
Parallel operation > Maximum tap
difference
.
2.
Enter the maximum tap difference.
3.
Press the
Accept
button to save the modified parameter.
Assigning a CAN bus address
You can use this parameter to assign a CAN bus address to the device. So
that all devices can communicate using the CAN bus, each device requires a
unique identifier. If the value is set to 0, then no communication takes place.
1.
Go to
Settings > Parameters > Parallel operation > CAN bus ad-
dress
.
2.
Enter CAN bus address.
3.
Press the
Accept
button to save the modified parameter.
6.6.3
Summary of Contents for TRAFOGUARD ISM
Page 1: ...Monitoring System TRAFOGUARD ISM Operating Instructions 5163667 00 EN ...
Page 222: ......
Page 223: ......