7 Operation
Maschinenfabrik Reinhausen GmbH 2020
44
1800138/08 EN
TAPMOTION
®
ED
Operation
Operating the motor-drive unit remotely
Operate the motor-drive unit remotely during normal operation.
You can do this with a single control pulse, e.g. using a voltage regulator of
the TAPCON® series.
This operation is always completed regardless of any other control pulses
emitted during the tap-change operation. In the standard design, the next
tap-change operation can only proceed once all control devices have
reached their resting positions.
Behavior in the event of a voltage interruption
If the voltage is interrupted during a tap-change operation, the motor-drive
unit will complete the started tap-change operation once the voltage supply
returns.
Operating motor-drive unit locally
In special operating cases (such as during maintenance tasks) the motor-
drive unit can also be operated electrically on site via control switch S3.
In exceptional cases, the unit can be operated using a hand crank. You will
find more information in the following section.
7
7.1
7.2