8 Operation
Maschinenfabrik Reinhausen GmbH 2020
232
3587317/21 EN
TAPCON
®
8.22.4 Displaying maintenance overview
The maintenance overview displays the progress of the individual mainte-
nance intervals. You can also see the limit values for the "yellow" and "red"
event messages. For the maintenance intervals of the on-load tap-changer,
the device uses the recorded operating data to predict the date for the next
maintenance appointment. The date is not displayed until enough operating
data has been recorded.
If you have deactivated the "OLTC operator maintenance" or "Transformer
operator maintenance" interval, the interval is shown grayed out in the main-
tenance overview.
Figure 163: Maintenance overview
► Go to
Information > System > Maintenance
.
8.23 Configuring analog inputs and outputs (optional)
You can flexibly configure the device's analog inputs and outputs and assign
device functions.
The device supports analog sensors with linear characteristic curves and
only outputs analog signals with linear characteristic curves.