8 Operation
Maschinenfabrik Reinhausen GmbH 2020
209
3587317/21 EN
TAPCON
®
Setting
Behavior
Auto/manual blocking
▪ The
Reversal of power flow
event is issued.
▪ If Z compensation is activated, this function is deacti-
vated.
▪ Automatic regulation is blocked.
▪ You cannot perform tap-change operations in manual
mode.
Target tap position
▪ The
Reversal of power flow
event is issued.
▪ If Z compensation is activated, this function is deacti-
vated.
▪ The device triggers a tap-change operation to the tap
position you defined in the "Target tap position" pa-
rameter.
▪ The device blocks further tap-change operations.
▪ The target-tap-position operation is ignored if there is
no tap-position capture. Automatic regulation is
blocked.
Table 74: Behavior in the event of a reversal of power flow
8.19.5 Tap position monitoring (optional)
You can set 2 limit values for tap position monitoring:
▪ Pos<
▪ Pos>
You can set the following parameters for each limit value.
▪ Delay time limit value
▪ Behavior limit value
Settings
Parameters
Tap posi...ing
Name
Value
Number of tap-change operations
775571
Pos<
1
Pos< delay time
0.0 s
Pos< behavior
Off
Pos>
26
Pos> delay time
0.0 s
Pos> behavior
Off
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin
29.01.2020 15:45
Figure 144: Tap position monitoring
1. Go to
Settings > Parameters > Grid > Tap position monitoring
.
2. Select the desired parameter.