8 Operation
Maschinenfabrik Reinhausen GmbH 2020
176
3587317/21 EN
TAPCON
®
Settings
Parameters
Compensation
Name
Value
Compensation method
R & X compensation
Ohmic resistance load
0.0 Ohm/m
Inductive resistance load
0.0 Ohm/m
Length of line
0.00 m
Voltage increase
0.0 %
Voltage limit value
0.0 %
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin
03.02.2020 08:09
Figure 121: Compensation
1. Go to
Settings > Parameters > Grid > Compensation
.
2. Select the desired parameter.
3. Set the desired parameter.
4. Press the
Accept
button to save the modified parameter.
Compensation method
You can use this parameter to set the compensation method.
Voltage increase
You can use this parameter to set the current-dependent voltage increase
∆U.
Voltage limit value
You can use this parameter to define the maximum permissible voltage in-
crease to avoid excess voltage on the transformer.
8.17 Tap position capture
The current tap position of the on-load tap-changer is transmitted from the
motor-drive unit to the device. You can define the type of tap position cap-
ture during the order. You cannot change this subsequently via a menu.
In accordance with your order, the tap position is transmitted in one of the
following ways:
▪ Digital signal
– BCD
– Dual code
– Gray code